4 commissioning – Lenze SL User Manual
Page 32

32
Lenze 13466147 EDBSM01 v19 EN
4 Commissioning
No.
Parameter Name
Range of Adjustment
Factory
Default
12
TB-13E INPUT
FUNCTIONS
NONE (01)
0-10 VDC (02)
4-20 mA (03)
PRESET SPEED #3 (04)
INCREASE FREQ (05)
START FORWARD (06)
EXTERNAL FAULT (07)
INVERSE EXT FAULT (08)
AUX. STOP (09)
ACCEL/DECEL #2 (10)
NONE (01)
TB-13E OUTPUT
FUNCTIONS
RUN (11)
FAULT (12)
INVERSE FAULT (13)
FAULT LOCKOUT (14)
AT SET SPEED (15)
ABOVE PRESET #3 (16)
CURRENT LIMIT (17)
AUTO SPEED (18)
REVERSE (19)
DYNAMIC BRAKING (20)
OTHER FUNCTIONS
REMOTE KEYPAD (21)
14
CONTROL
TERMINAL STRIP ONLY (01)
REMOTE KEYPAD ONLY (02)
TERMINAL STRIP
ONLY (01)
16
UNITS EDITING
TENTHS OF UNITS (01)
WHOLE UNITS (02)
WHOLE
UNITS (02)
17
ROTATION
FORWARD ONLY (01)
FORWARD AND REVERSE (02)
FORWARD
ONLY (01)
18
MOTOR OVERLOAD
TYPE
SPEED COMPENSATION (01)
NO SPEED COMPENSATION (02)
SPEED
COMP. (01)
19
ACCELERATION TIME
0.1 - 3600.0 SEC
20.0 SEC
20
DECELERATION TIME
0.1 - 3600.0 SEC
20.0 SEC
21
DC BRAKE TIME
0.0 - 3600.0 SEC
0.0 SEC
22
DC BRAKE VOLTAGE
0.0 - 30.0 %
0.0 %
23 MINIMUM FREQUENCY
0.0 - MAXIMUM FREQUENCY
0.0 Hz
24 MAXIMUM FREQUENCY
MINIMUM FREQUENCY - 240 Hz
SCL = 50.0 Hz
SCM = 60.0 Hz
25
CURRENT LIMIT
30 - 180 %
180 %
26
MOTOR OVERLOAD
30 - 100 %
100 %
27
BASE FREQUENCY
25.0 - 500.0 Hz
SCL = 50.0 Hz
SCM = 60.0 Hz