7 troubleshooting and fault elimination, 1 fault messages, Troubleshooting and fault elimination – Lenze EPM−H310 User Manual
Page 62: Fault messages, 7troubleshooting and fault elimination
Troubleshooting and fault elimination
Fault messages
7
l
62
EDBPM−H310 DE/EN/FR 7.1
7
Troubleshooting and fault elimination
7.1
Fault messages
Call up the status messages of the operating unit to display the fault message
that occurred last. (
¶ 58)
Display
Fault
Cause
Remedy
NO ERROR
No fault
−
−
PR ERROR
Faulty data
exchange
Connection between operating
unit and PC is faulty
l
Check that the connections are
firmly seated.
l
Check cable for damages
COM BROK
Communication
interrupted
Serial data cable between
operating unit and PC is
defective or not correctly
connected
l
Check Sub−D connector for correct
connection and firm seating.
l
Replace serial data cable
ASIC ko1
Communication
with system
bus (CAN)
interrupted
l
Faulty wiring (e. g. polarity)
of the system bus
l
Faulty parameterisation of
interface (baud rate,
address, identifier)
l
Check wiring of system bus (CAN)
(
^
l
Check parameter setting (
^
HMI
Designer − Getting started).
ASIC ko2
ASIC ko3
ASIC ko4
RESET
SDOERR 6
SDOERR 5
SDOERR 3