Resetting system error messages, Troubleshooting and fault elimination – Lenze EVS93xx User Manual
Page 45

Troubleshooting and fault elimination
System error messages
Resetting system error messages
l
45
EDKVS93−02 EN 3.0
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
x252
AddData
DlErr
Error during FLASH memory
access
An error occurred when
downloading the data into the
FLASH memory (e.g. time−out,
transmission error, mains failure
during transmission)
Check/repeat data transfer.
x260
Err Node
Guard
"Life guarding event"
The controller configured as a
CAN slave does not receive a
"Node Guarding" telegram from
the CAN master within the "Node
Life Time".
l
Check wiring at X4.
l
Check CAN configuration.
l
Ensure that "node guarding"
has been activated in the CAN
master
l
Adapt the "node life time"
(C0383) to CAN master setting.
Explanation of the error numbers:
x
0 = TRIP, 1 = message, 2 = warning, 3 = FAIL−QSP
e.g. "2091": An external monitoring has triggered the warning EEr
4.3.2
Resetting system error messages
Reaction
Measures to reset the fault message
TRIP/ FAIL−QSP
Note!
If a TRIP/FAIL QSP source is still active, the pending TRIP/FAIL QSP cannot be reset.
The TRIP/FAIL QSP can be reset by:
l
pressing
ð S on keypad XT EMZ9371 BC. Then, press U to re−enable the controller.
l
Set code C0043 = 0.
l
Control word C0135, bit 11
l
Control word AIF
l
Control word system bus (CAN) / MotionBus (CAN) at ECSxS/P/M
After the reset of the TRIP/FAIL QSP, the drive remains at standstill.
Message
Danger!
The fault message is reset automatically after the fault has been eliminated, and the drive
restarts automatically.
Warning
After the fault has been eliminated, the fault message is reset automatically.