Troubleshooting and fault elimination
System error messages
General error messages
l
39
EDKVS93−02 EN 3.0
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
0078
PR4
Checksum error in parameter
set 4
PLEASE NOTE: The Lenze setting is
loaded automatically!
l
Fault while loading a
parameter set.
l
Interruption during the
transfer of the parameter set
via keypad.
l
Set the required parameters
and save them with C0003 = 4.
The parameters saved do not
comply with the software version
loaded.
In order to be able to
acknowledge the error, first save
the parameter set with C0003 = 4.
0079
PI
Fault during parameter
initialisation
l
An error has been detected
during the parameter set
transfer between two devices.
l
The parameter set does not
match the controller, e.g. if
data has been transferred from
a higher−power controller to a
lower−power controller.
l
Correct parameter set.
l
Send parameter set (on floppy
disk/CD−ROM) and a detailed
description of the problem to
Lenze.
0080
PR6
Too many user codes
Reduce the number of user codes.
x082
Sd2
Resolver error at X7
Resolver cable interrupted.
l
Check cable for open circuit.
l
Check resolver.
l
Switch off the monitoring
(C0586 = 3).
x083
Sd3
Encoder error at X9
Cable interrupted.
Check cable for open circuit.
Pin X9/8 not connected.
Apply 5 V to pin X9/8 or switch off
monitoring (C0587 = 3).
x085
Sd5
Encoder error at X6/1 and X6/2
(C0034 = 1)
Current signal at X6/1 X6/2 <
2mA.
l
Check cable for open circuit.
l
Check current signal encoder.
l
Switch off monitoring
(C0598 = 3).
x086
Sd6
Motor temperature sensor error
(X7 or X8)
Encoder for detecting the motor
temperature at X7 or X8 indicates
undefined values.
l
Check cable for firm
connection.
l
Switch off the monitoring
(C0594 = 3).