Troubleshooting and fault elimination
System error messages
l
71
EDK10200EV3 DE/EN/FR 7.1
Remedy
Cause
Fault
Display
PC
1)
Keypad
H05
a
105
Internal fault
Contact Lenze
H08
a
108
Error when
configuring the
extension board
Extension board has not
been plugged−on correctly
or not supported by the
program
l
Check plug connection
l
Check if the extension board
is supported by the operating
system version
per
a
74
Error in program
flow
An error has been
detected in the program
flow.
Send Drive PLC with data set (to
floppy disk) to Lenze
pi
a
79
Initialisation error
during parameter
set transfer
l
During the parameter
set transfer to the
Drive PLC an error has
been detected
l
Wrong parameter set
for Drive PLC
Correct parameter set
Pr0
a
75
Internal fault
Contact Lenze
Pr1
a
72
PAR1 incorrectly
transferred via
keypad/PC
PAR1 is defective
Repeat data transfer or load
Lenze setting
Pr5
a
79
Internal fault
Save cyclic parameter set
Do not execute "Save cyclic
parameter set" since this
damages the EEPROM
1)
LECOM error number
)
Note!
Detailed information on the system error messages of the Drive PLC can be
found in the PDF manual "Drive PLC" (chapter Appendix: System error
messages)