Commissioning

Initial switch−on

5

EDK82ZAFLC−010 DE/EN/FR 4.0

45

l

H1inbet−statusanzeige

Step

Procedure

Description

1.

Configure the host system for communication with the function module.

2.

Check bus
termination

Only for the first and last station:
Activate bus terminating resistor with DIP switch = ON (

^ 43)

Lenze setting: OFF

3.

Connect mains
voltage and, if
required, the
separate voltage
supply for the
function module

The standard device is ready for operation after approx. 1 second.
Controller inhibit is active.
Reaction:

l

The green LED on the front of the function module illuminates
(only visible in case of 8200 vector,

^ 46).

l

Keypad:

dc

(if fitted)

4.

Assign station
address.

Assign a station address to the station using C1509.
Every station needs its own address.
Lenze setting: 1

5.

Set LECOM baud rate

Set LECOM baud rate via keypad or host system.
Lenze setting: 9600 Bit/s

6.

Communication with the controller is now possible, i.e. all codes can be read and all
writable codes can be changed.
If required adapt the codes to your application (see Operating Instructions for the standard
device).
The yellow LED on the function module flashes if the LECOM−B is active (

^ 46).

7.

Select function
module as setpoint
source

Setpoint source: C0046
Configuration: C0412/1 = 0

8.

Enable controller via
terminal.

Terminal 28 = HIGH

9.

Select setpoint

Setpoint selection through C0046

10.

The drive now starts.

)

Note!

If you set the station address (C1509) and the LECOM baud rate (C1516) in step
4. and 5. of commissioning via the host system, the settings for the host
system must be changed immediately. Otherwise the host system will not
recognise the responses since these are already sent with the new settings by
the controller.