4 technical data, General data, Operating conditions – Lenze E82ZAFPC201 User Manual
Page 52: Technical data, 4technical data

4
Technical data
General Data
EDK82ZAFPC-201 DE/EN/FR 6.0
52
H1_Daten-IP20
4
Technical data
General Data
Area
Values
Order designation
E82ZAFPC201
PUO ID number
0x081B
hex
Communication profile
(DIN 19245 Part 1 and Part 3)
PROFIBUS-DP-V0
PROFIBUS-DP-V1
Communication medium
RS485
Drive profile
DRIVECOM profile ”Drive technology 20” (can be switched off)
PROFIdrive (can be switched off, state machine and PROFIdrive
parameter data channel)
Network topology
Without repeaters: line
With repeaters: line or tree
PROFIBUS bus device
Slave
Baud rate [kbps]
9.6 ... 12000 (automatic detection)
Process data words
1 ... 10 words
(16 bits/word)
DP user data length
1 ... 10 process data words +
4 parameter data words
Max. number of bus devices
Standard: 32 (= 1 bus segment)
With repeaters: 125
Max. cable length per bus
segment
1200 m (depending on the baud rate and cable type used)
External DC voltage supply
+24 V DC ±10 %, max. 100 mA
Operating conditions
Ambient conditions
Climate
Storage
IEC/EN 60721-3-1
1K3 (-25 to +60 °C)
Transport
IEC/EN 60721-3-2
2K3 (-25 to +70 °C)
Operation
Corresponding to the data of the Lenze standard device used (see
documentation of the standard device).
Pollution
EN 61800-5-1
Degree of pollution 2
Degree of
protection
IP20 (protection against accidental contact according to NEMA 250 type 1)