9

ALSV01B

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

p441 Relay Output

TB-19, 20, 21

0

0

None

Disables the output

1

Run

Energizes when the drive is running

2

Reverse

Energizes when reverse rotation is active

3

Fault

De-energizes when the drive trips, or power is removed

4

Inverse Fault

Energizes when the drive trips

5

Fault Lockout

P110 = 3...6: De-energizes if all restart attempts fail

6

At Speed

Energizes when output frequency = commanded frequency

7

Above Preset Speed #6

Energizes when output frequency > P136

8

Current Limit

Energizes when motor current = P171

9

Follower Loss (4-20 mA)

Energizes when 4-20 mA signal falls below 2 mA

10 Loss of Load

Energizes when motor load drops below P145; Refer to
P146 also

11 Local Keypad Control Active

Energizes when the selected source is active for start
control

12 Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference Active

Energizes when P101 reference is active

16 Auto Reference Active

Energizes when Auto Reference is activated using TB-13
input; refer to P121...P124

17 Sleep Mode Active

Refer to P240...P242

18 PID Feedback < Min. Alarm

Energizes when PID feedback signal < P214

19 Inverse PID Feedback < Min. Alarm

De-energizes when PID feedback signal < P214

20 PID Feedback > Max Alarm

Energizes when PID feedback signal > P215

21 Inverse PID Feedback > Max Alarm

De-energizes when PID feedback signal > P215

22 PID Feedback within

Min/Max Alarm range

Energizes when PID feedback signal is within the Min/Max
Alarm range; refer to P214, P215

23 PID Feedback outside

Min/Max Alarm range

Energizes when PID feedback signal is outside the Min/Max
Alarm range; refer to P214, P215

24 Reserved
25 Network Activated

Requires 15HP (11kW) or higher drive.
No function for 0.33-10HP (0.25kW-7.5kW) drives.

26 Loss of 0-10V Input

Energizes when 0-10V signal < P158

27 Sequencer Controlled

State set in individual sequencer segments

28 Sequencer Active
29 Sequencer Suspended
30 Sequence Done

End sequence

31 Output Frequency = 0.0Hz

Output inactive

P144 Digital Output

Inversion

P144

Invert

P441

Invert

P142

Invert

P140

0

NO

NO

NO

1

NO

NO

YES

2

NO

YES

NO

3

NO

YES

YES

4

YES

NO

NO

5

YES

NO

YES

6

YES

YES

NO

7

YES

YES

YES

Used to invert the selections for P140, P441 (Relay Output)
and P142 (TB-14 Output).
EXAMPLE: When P140 = 6 (AT SPEED), the relay is
energized when output frequency = commanded
frequency. IF P144=1, 3, 5 or 7, then P140 is inverted
(INVERSE AT SPEED) and the relay is energized when the
output frequency does

not equal the command frequency.

NOTE
Inverting P140, P142 or P441 when the parameter is set to NONE (0) will result in the output being
energized continuously.