Commissioning
4
Commissioning
4.1 Network Parameters (P400)
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p400 Network Protocol
0 Not Active
This parameter setting is based upon the
network or I/O module that is installed.
1 Remote Keypad
2 Modbus RTU
3 CANopen
4 DeviceNet
5 Ethernet
6 Profibus
7 Lecom-B
8 I/O Module
p401 Module Type Installed
0
0 No Module Installed
Module type format: 0xAABC; Drive Display:
AA.B.C
AA = Module Type
B = Major revision
C = minor revision
1 Basic I/O (0x0100, 1.0.0)
2 RS485/Rem. Keypad (0x0200, 2.0.0)
3 CANopen (0x0300, 3.0.0)
11 PROFIBUS (0x1100, 11.0.0)
12 Ethernet (0x1200, 12.0.0)
P402
Module Status
0
0 Not Initialized
1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online
4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed
Module type mismatch P401
7 Initialization Error
Protocol selection mismatch P400
P403
Module Reset
0
0 No Action
Returns module parameters 401…499 to the
default values shown in the manual
1 Reset parameters to default values
P404
Module Timeout Action
0
0 No Fault
Action to be taken in the event of a Module/
Drive Time-out.
Time is fixed at 200ms
STOP is by the method selected in P111.
1 STOP (see P111)
2 Quick Stop
3 Fault (F_ntF)
P405
Current Network Fault
0 No Fault
1 F.nF1
NetIdle Mode
2 F.nF2
Loss of Ethernet I/O connection
3 F.nF3
Network Fault
4 F.nF4
Explicit Message Timeout
5 F.nF5
Overall Network Timeout
6 F.nF6
Overall Explicit Timeout
7 F.nF7
Overall I/O Message Timeout
P406
Proprietary
Manufacturer specific
p407 … P499
Module Specific Parameters
Refer to the Communications Reference Guide
specific to the network or I/O module installed.
NOTE
Set P400 = 8 for the SMVector drive to communicate with the additional I/O module.