Technical data, Analog inputs, Measuring circuit monitoring – JUMO 14597 safetyM TB/TW - Temperature Limiter and Temperature Monitor Data Sheet User Manual
Page 2
2011-12-31/00506174
Data sheet 701160
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Seite 2/8
Technical data
Analog inputs
RTD temperature probe
thermocouples
DC voltage, DC current
Measuring circuit monitoring
Designation
Measuring range
Accuracy
1
Pt 100 EN 60751
-200 … +850°C
0.1%
KTY11-6 PTC
-50 ... 150°C
1%
Pt 1000 DIN
-200 … +850°C
0.1%
connection types
2-wire, 3-wire circuits
Sampling
210ms
Input filter
2nd order digital filter; filter constant adjustable from 0 to 100secs
Special features
2x Pt100 for differential measurement, display can also be programmed in °F
Designation
Measuring range
Accuracy
1
Fe-CuNi "L" DIN 43710
-200 to +900°C
0.4%
Fe-CuNi "J" EN 60584
-200 to +1200°C
0.4%
Cu-CuNi "U" DIN 43710
-200 to +600°C
0.4%
Cu-CuNi "T" EN 60584
-200 to +400°C
0.4%
NiCr-Ni "K" EN 60584
-200 to +1372°C
0.4%
NiCrSi-NiSi "N" EN 60584
-100 to +1300°C
0.4%
Pt10Rh-Pt "S" EN 60584
0 to +1768°C
0.4%
Pt13Rh-Pt "R" EN 60584
0 to +1768°C
0.4%
Pt30Rh-Pt6Rh "B" EN 60584
300 to 1820°C
0.4%
W3Re-W25Re "D"
0 ... 2495°C
0.4%
Cold junction
Pt 100, internal
Cold junction accuracy
± 1K
Sampling rate
210 ms
Input filter
2nd order digital filter; filter constant adjustable from 0 to 100secs
Special features
also programmable in °F
1. Accuracy refers to the maximum extent of the measuring range.
If the measuring range is smaller, the linearisation accuracy is reduced .
Measuring range
Accuracy
0 to 20mA, voltage drop < 2 V
4 to 20mA, voltage drop < 2 V
0.2%
0 to 10V, input resistance > 100 k
Ω
2 to 10V, input resistance > 100 kW
0.1%
Scaling
freely programmable within the limits
Sampling rate
210 ms
Input filter
2nd order digital filter; filter constant adjustable from 0 to 100secs
RTD temperature probe
and KTY11-6
Twin thermocouples
Thermocouples
Current 0 to 20 mA, 4 to 20mA
Voltage 0 to 10 V, 2 to 10 V
Overrange and un-
derrange
is detected
LEDs K1 and KV light up; "1999" flashes in the display
Probe and lead break is detected
LEDs K1 and KV light up; "1999" flashes in the display; relay K1 is active.
is detected at 4 to 20mA
and 2 to 10V
LEDs K1 and KV light up;
"1999" flashes in the display
Relay K1 is inactive
Probe short circuit
is detected
LEDs K1 and KV light up;"1999" flashes in the display
Relay K1 is inactive
is not detected