Technical data, Analog inputs, Measuring circuit monitoring – JUMO 14597 safetyM TB/TW - Temperature Limiter and Temperature Monitor Data Sheet User Manual

Page 2

background image

2011-12-31/00506174

Data sheet 701160

JUMO GmbH & Co. KG • 36035 Fulda, Germany

Seite 2/8

Technical data

Analog inputs

RTD temperature probe

thermocouples

DC voltage, DC current

Measuring circuit monitoring

Designation

Measuring range

Accuracy

1

Pt 100 EN 60751

-200 … +850°C

0.1%

KTY11-6 PTC

-50 ... 150°C

1%

Pt 1000 DIN

-200 … +850°C

0.1%

connection types

2-wire, 3-wire circuits

Sampling

210ms

Input filter

2nd order digital filter; filter constant adjustable from 0 to 100secs

Special features

2x Pt100 for differential measurement, display can also be programmed in °F

Designation

Measuring range

Accuracy

1

Fe-CuNi "L" DIN 43710

-200 to +900°C

0.4%

Fe-CuNi "J" EN 60584

-200 to +1200°C

0.4%

Cu-CuNi "U" DIN 43710

-200 to +600°C

0.4%

Cu-CuNi "T" EN 60584

-200 to +400°C

0.4%

NiCr-Ni "K" EN 60584

-200 to +1372°C

0.4%

NiCrSi-NiSi "N" EN 60584

-100 to +1300°C

0.4%

Pt10Rh-Pt "S" EN 60584

0 to +1768°C

0.4%

Pt13Rh-Pt "R" EN 60584

0 to +1768°C

0.4%

Pt30Rh-Pt6Rh "B" EN 60584

300 to 1820°C

0.4%

W3Re-W25Re "D"

0 ... 2495°C

0.4%

Cold junction

Pt 100, internal

Cold junction accuracy

± 1K

Sampling rate

210 ms

Input filter

2nd order digital filter; filter constant adjustable from 0 to 100secs

Special features

also programmable in °F

1. Accuracy refers to the maximum extent of the measuring range.
If the measuring range is smaller, the linearisation accuracy is reduced .

Measuring range

Accuracy

0 to 20mA, voltage drop < 2 V
4 to 20mA, voltage drop < 2 V

0.2%

0 to 10V, input resistance > 100 k

Ω

2 to 10V, input resistance > 100 kW

0.1%

Scaling

freely programmable within the limits

Sampling rate

210 ms

Input filter

2nd order digital filter; filter constant adjustable from 0 to 100secs

RTD temperature probe
and KTY11-6

Twin thermocouples

Thermocouples

Current 0 to 20 mA, 4 to 20mA
Voltage 0 to 10 V, 2 to 10 V

Overrange and un-
derrange

is detected
LEDs K1 and KV light up; "1999" flashes in the display

Probe and lead break is detected

LEDs K1 and KV light up; "1999" flashes in the display; relay K1 is active.

is detected at 4 to 20mA
and 2 to 10V
LEDs K1 and KV light up;
"1999" flashes in the display
Relay K1 is inactive

Probe short circuit

is detected
LEDs K1 and KV light up;"1999" flashes in the display
Relay K1 is inactive

is not detected