Operating data
Case
Hysteresis
in % of the control /
limit value range
Switching function
with fluid-filled measuring system
Rated value
Possible actual value
TR, TW
3
3 max. 4
standard
6
6 max. 8
on request
1.5
1 max. 2
Surcharge
with gas-filled measuring system
5
4 max. 8
standard
9
8 max. 12
on request
2
1.5 max. 2.5
Surcharge
with fluid-filled measuring system
STW (STB)
5
4 max. 6
standard
9
8 max. 11
on request
2
1 max. 3
Surcharge
with gas-filled measuring system
7
5 max. 12
standard
9
8 max. 16
on request
2
1.5 max. 3
Surcharge
Switching point accu-
racy in % of the con-
trol/limit value range
TR, TW: in the upper third of the scale ± 1.5%, at scale beginning ± 6%
STB, STW (STB): in the upper third of the scale +0/-5%, at scale beginning +0/-10%
Ambient
temperature influence
based on the
control/
limit value range
When the ambient temperature on the case deviates from the calibration ambient temperature 22 °C,
a switch point offset occurs.
Higher ambient temperatures = lower switching point
Lower ambient temperature = higher switching point
Surface-mounting thermostats with scale limit value
< 200 °C
÷ 200 °C ≤ 350 °C
> 350 °C ≤ 500 °C
TR / TW
STB/STW (STB)
TR / TW
STB/STW (STB)
TR / TW
STB/STW (STB)
Influence on the switch head
0.08%/K
0.17%/K
0.06%/K
0.13%/K
0.14%/K
0.12%/K
Influence on the capillary per metre
0.047%/K
0.054%/K
0.09%/K
0.11%/K
0.04%/K
0.03%/K
admissible storage
temperature
-50 to +50 °C
admissible
ambient
temperature
during use
max. +80 °C
Rated position
as per DIN 16 257, NL 0 to NL 90 (different rated positions (NL) on request)
serial
Case lid: Polycarbonate, shock resistant
Case bottom part: Aluminum die casting, painted
Color: pebble gray RAL 7032
Color: anthracite gray RAL 7015
Extra code "701"
Case lid made of aluminum die casting, painted
Color: pebble gray RAL 7032
Set point value setting TR:
Switching point adjustable from the outside using the rota-
ry knob
TW, TB, STB, STW (STB):
The switching point can be adjusted by means of a screw-
driver once the case lid has been removed
Protection type
EN 60 529-IP 54
Cable inlet
As a standard: self-sealing grommet M 20 x 1.5, sealing range 8-10 mm
Weight
approx. 0.8 kg
Switch head
fastening
ATHf- type series . .
with capillary
serial
Screw-connection by means of counter nut M 18 x 1 on the case stud,
capillary outlet on the case stud
Extra code
711
with 2 screws through the case bottom part, lateral capillary outlet on the case,
lid and bottom part made of plastic
764
Fastening flange made of steel sheet, capillary outlet on the case stud
248
Wall stands