Display and measuring accuracy
All specifications refer to the controller nominal data.
Permissible load current depending on the ambient temperature and installation height
Supply voltage: ±
2,5%
Load current: ±
1%
Load voltage:
±
1% Power:
±
2%
Analog input
Voltage/current: ±
1%
Analog output
Voltage/current: ±
1%
Load resistance: ±
2%
(for resistive load)
12
11
+
–
Note:
At a device temperature of 105°C, the load current is reduced
for each degree of temperature increase.
The power controller current is switched off completely at a
device temperature of >115°C.
45
50
60
75
20
200
T/°C
150
Load current in A
Reduction at a temperature of 45 °C:
2 %/kelvin
70 %
250
100
50
Note:
In the case of air cooling, it must be noted that the
effectiveness of the cooling is reduced the higher up the
device is installed. As a result, the current carrying capacity
of the SCR power controller decreases with such a cooler
as the installation height increases as shown in the image.