2012-12-31/00561067

Data sheet 709061

Page 2/21

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

Technical data

Voltage supply, load current

Analog inputs

Binary inputs

Binary outputs, actual value output

Code

Voltage supply for control electronics = max. load voltage

Fan specifications
Type 709061/X-0X-250...

024

AC 24V -20%...+15%, 45 ...63 Hz

AC 24V/30VA

042

AC 42V -20%...+15%, 45 ...63 Hz

AC 24V/30VA

115

AC 115V -20%...+15%, 45 ...63 Hz

AC 115V/30VA

230

AC 230V -20%...+15%, 45 ...63 Hz

AC 230V/30VA

265

AC 265V -20%...+15%, 45 ...63 Hz

AC 230V/30VA

400

AC 400V -20%...+15%, 45 ...63 Hz

AC 230V/30VA

460

AC 460V -20%...+15%, 45 ...63 Hz

AC 230V/30VA

500

AC 500V -20%...+15%, 45 ...63 Hz

AC 230V/30VA

Load current I

L rms

AC 20, 32, 50, 100, 150, 200, 250A

Load type

Resistive and resistive/inductive loads

Control section power consumption

max. 20 VA

Control signal

0(4) … 20mA

R

i

= 50

Ω

0(2) … 10V

R

i

= 25k

Ω

0(1) … 5V

R

i

= 25k

Ω

Default set point
value

Via standard signals (current, voltage) or interface

Base load:

Output as minimum control value

Maximum control value:

Output as maximum control value

Example
P control:

Binary input 1, 2

For connection to potential-free contact or optocoupler, voltage proof up to DC 12V

Relay (changeover contact)
without contact suppression

150000 switching actions at a contact rating of 3A/230V 50Hz (resistive load)

Optocoupler output

I

Cmax

= 2mA, U

CEOmax

= 32V

Actual value output

Switched off as standard.
For standard signal, voltage: 0 … 10V , 2 … 10V, 0 … 5V to 1 … 5V
For standard signal,

current: 0 … 20mA to 4 … 20mA (burden max. 500

Ω)

Depending on the device type, the output of various internal measuring values such as load current, load
voltage or power is possible.

Thyristor firing re-
quest:

setpoint specification
Current input
(current proof up to 25mA)

setpoint specification
Voltage input
(voltage proof up to DC 32V)

setpoint specification
Binary input1, 2
(voltage proof up to DC 32V)

via Interface

continous

The power controller provides the power for the load conti-
nuously depending on the default setpoint value.

-

possible

logic
(Solid State Relais
SSR)

The power controller acts like a switch and provides the power
by either switching ON or OFF. The switching level is always in
the middle of the selected input range.
At 4 to 20mA it is 12mA, at 0 to 10V it is 5V.

OFF logic level „0“ = 0 to +0,8V;
ON logic level 1 = +2 to 3,3V

possible

Control signal

P

Base load: 680 W

Maximum
Output level: 3680 W

0 mA

20 mA

3000W

0...20mA

־

Base load