beautypg.com

Johnson Systems DE90-3000 Series Retrofit Control System User Manual

Page 20

background image

www.johnsonsystems.com

20

INF HOLD
Displayed when DMX is disconnected and the systems predetermined DMX status hold (SH) time

is set for infinite (INF) hold. Refer to menu item “SH TIME” on page 27 for further details.
SCENE:XX
Displays the scene (1 to 24) that is currently activated. Refer to menu item “L-BUTTON”

on page 30 for further details.
A-SCENE!
Displayed when the auxiliary input is triggered. Refer to menu item “AUX IN”

on page 30 for further details.
FIRE!!!
Displayed when the fire alarm input is triggered. Refer to menu item “F-ALARM”

on page 31 for further details.
SECURITY
Displayed when the security alarm input is triggered. Refer to menu item “S-ALARM”

on page 31 for further details.
EXT-TEMP
Displayed when the over-temp input is triggered or when the OEM thermostat in the DE90

dimmer rack senses an over-temperature condition of 185°F ±7°F (85°C ±4°C). All dimmer

outputs are disabled and the fans are turned on to full until the external devices temperature

drops to within specification.
REM-TEMP
Displayed when the systems remote temperature sensor measures an over-temperature

condition of 185°F (85°C) or more. All dimmer outputs are disabled and the fans are turned on

to full until the temperature cools down to 178°F (81°C) or less. The remote temperature sensor

is not used with DE90-3000 Series retrofit control systems. Refer to menu item “REM TEMP” on

page 32 to view the current remote temperature.
CTL-TEMP
Displayed when the microcontroller senses an internal over-temperature condition of 185°F

(85°C) or more. All dimmer outputs are disabled and the fans are turned on to full until the

temperature cools down to 178°F (81°C) or less. Refer to menu item “CTL TEMP” on page 32 to

view the current microcontroller temperature.
Ø ERROR!
Displayed when an error is sensed on any of the input power phases. A phase error can be

caused from an under-voltage of less than 100VAC, an over-voltage of greater than 130VAC,

or if a zero-cross phase reference is not detected.
RTC ERR!
Displayed when the system detects a runtime counter (RTC) error. This occurs when there

is an invalid hard-key code and the runtime counter is greater than 2160 hours (90 days).

Refer to menu item “HARD-KEY” on page 33 for further details.
LOCKED!!
Displayed when an attempt is made to access the system configuration menu items and the

programming switches are locked out. To toggle between “LOCKED!!” and “UNLOCKED” press

and hold down the “EXECUTE” and then “ESCAPE” switches at the same time for 4-5 seconds.

Also displayed when an attempt is made to access factory only setup menus.