Bryant 701A User Manual
Page 3

Fig. 2—701A030-042 and 702A030, 036 Unit Dimensions
UNIT
ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. (MM)
”A”
CENTER OF GRAVITY
IN. (MM)
lb.
kg
X
Y
Z
701A030
208/230-3-60
258
117.0
35.02 (889.5)
19.0 (482.6)
14.0 (355.6)
15.0 (381.0)
701A036
208/230-3-60, 460-3-60
268
121.6
37.02 (940.3)
20.0 (508.0)
14.0 (355.6)
13.0 (330.2)
701A042
208/230-3-60, 460-3-60
294
133.3
35.02 (889.5)
19.0 (482.6)
14.0 (355.6)
13.0 (330.2)
702A030
208/230-3-60
291
132.0
39.02 (991.1)
19.5 (495.3)
15.5 (393.7)
17.6 (447.0)
702A036
208/230-3-60, 460-3-60
299
135.6
35.02 (889.5)
19.5 (495.3)
15.25 (387.4)
16.5 (419.1)
C99007
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
INCHES [mm]
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................42.00 [1066.8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
INCHES [mm]
TOP OF UNIT ...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
INCHES [mm]
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
—3—