Fig. 2—701A030-042 and 702A030, 036 Unit Dimensions

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

IN. (MM)

”A”

CENTER OF GRAVITY

IN. (MM)

lb.

kg

X

Y

Z

701A030

208/230-3-60

258

117.0

35.02 (889.5)

19.0 (482.6)

14.0 (355.6)

15.0 (381.0)

701A036

208/230-3-60, 460-3-60

268

121.6

37.02 (940.3)

20.0 (508.0)

14.0 (355.6)

13.0 (330.2)

701A042

208/230-3-60, 460-3-60

294

133.3

35.02 (889.5)

19.0 (482.6)

14.0 (355.6)

13.0 (330.2)

702A030

208/230-3-60

291

132.0

39.02 (991.1)

19.5 (495.3)

15.5 (393.7)

17.6 (447.0)

702A036

208/230-3-60, 460-3-60

299

135.6

35.02 (889.5)

19.5 (495.3)

15.25 (387.4)

16.5 (419.1)

C99007

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

INCHES [mm]

EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................42.00 [1066.8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

INCHES [mm]

TOP OF UNIT ...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]

NEC. REQUIRED CLEARANCES.

INCHES [mm]

BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]

—3—