Bryant 559F User Manual
Page 4

—
4
—
NOTES FOR FIG. 1, 3, 5, 7
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. On 208/230-v unit, TRAN1 is factory wired to ORN lead for 230-v
power supply. If unit is to be run on 208-v power supply, TRAN1 must
be rewired. Disconnect the BLK wire on TRAN1 and connect wire to
208-v RED wire. Insulate 230-v ORN wire.
5. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
6. The CLO locks out the compressor to prevent short cycling on com-
pressor overload and safety devices. Before replacing CLO, check
these devices.
7. Jumpers are omitted when unit is equipped with an economizer.
8. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An under-
lined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.
NOTES FOR FIG. 2, 4, 6, 8
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. Jumpers are omitted when unit is equipped with an economizer.
5. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
6. The CLO locks out the compressor to prevent short cycling on com-
pressor overload and safety devices. Before replacing CLO, check
these devices.
7. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An under-
lined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.
NOTES FOR FIG. 9, 11, 13, 15
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. Jumpers are omitted when unit is equipped with an economizer.
4. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
5. On 208/230-v unit, TRAN1 is factory wired to ORN lead for 230-v
power supply. If unit is to be run on 208-v power supply, TRAN1 must
be rewired. Disconnect the BLK wire on TRAN1 and connect wire to
208-v RED wire. Insulate 230-v ORN wire.
6. The CLO locks out the compressor to prevent short cycling on com-
pressor overload and safety devices. Before replacing CLO, check
these devices.
7. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An under-
lined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.
NOTES FOR FIG. 10, 12, 14, 16
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. Jumpers are omitted when unit is equipped with an economizer.
4. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
5. If unit is to be run on 460-v power supply, TRAN1 must be wired to
BLK wire.
6. The CLO locks out the compressor to prevent short cycling on com-
pressor overload and safety devices. Before replacing CLO, check
these devices.
7. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An under-
lined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.