Operating Instructions Safety Switch Evaluation Unit CMS-E-AR

Technical data

Parameter

Value

Unit

Housing material

Polyamide PA6.6

Dimensions

89 x 79.4 x 25

mm

Weight

0.13

kg

Ambient temperature

0 ... +50

°C

Storage temperature

-25 ... +70

°C

Degree of protection acc. to EN 60529

Terminals IP20 / housing IP40

Degree of contamination

2

Mounting

Mounting rail 35 mm acc. to DIN EN 60715 TH35

Number of read heads

1 ... 30 serial

1)

/ 2 parallel

Connection

Plug-in connection terminals

Operating voltage U

B

24 ±10%

V DC

Internal fuse (operating voltage U

B

)

750 (automatically resetting fuse PTC)

mA

Safety contact

1

Switching voltage U

max.

250

V AC

Typ. current consumption

70

mA

Switching current I

max.

at 24 V

3

A

Switching current, I

min.

at 24 V

2

mA

Breaking capacity P

max.

750

VA

External contact fuse (safety circuit)

acc. to EN IEC 60269-1

3

A gG

Utilization category

I

e

2)

U

e

2)

according to EN 60947-5-1 AC-1

3 A

250 V

AC-15

0.9 A

250 V

DC-13

1.8 A

24 V

Switching load acc. to UL Class 2

Input:

24 V

AC/DC

Output:

30 V

AC

24 V

DC

Rated insulation voltage U

i

250

V AC

Vibration resistance

According to EN 60947-5-2

Mechanical operating cycles, relay

10 x 10

6

EMC compliance

According to EN 60947-5-3

Risk time according to EN 60947-5-3

10

ms

Reliability values according to EN ISO 13849‑1
as a function of the switching current

at 24 V DC

0.1

1

3

A

Number of switching cycles/year

< 96,000

< 75,000

< 18,000

Mission time

20

years

Category

2 read heads

3

>2 read heads

1

Performance Level (PL)

2 read heads

d

>2 read heads

c

PFH

d

2 read heads

4.3 x 10

--8

>2 read heads

1.1 x 10

-6

1) For 3 m cable lengths. The number depends on the cable length.

2) I

e

= max. switching current per contact, U

e

= switching voltage

Combination options

Design

Read head

Circuit

diagram not

actuated

3)

Actuator

Assured

switch‑on

distance s

ao

[mm]

4)

Assured

switch‑off

distance s

ar

[mm]

Evaluation unit CMS

‑E

‑AR

CMS-R-AXD/-SC

BN

BK (YE)

WH

BU (GN)

CMS-M-AB

6

18

CMS-R-AXE/-SC

CMS-M-AG

18

34

CMS-R-AXF/-SC

BN

WH

CMS-M-AB

6

18

CMS-R-AXG/-SC

CMS-M-AG

18

34

5)

CMS-R-AXR

BN

BK (YE)

WH

PK

GY

BU (GN)

Rv

CMS-M-AI

9

(7)

6)

23

(15)

6)

CMS-R-BXO/-SC

BN

BK (YE)

WH

BU (GN)

CMS-M-BH

6

17

CMS-R-BXP/-SC

BN

WH

M25

CMS-R-CXA/-SC

BN

BK (YE)

WH

BU (GN)

CMS-M-CA

7

16

CMS-R-CXB/-SC

BN

WH

M30

CMS-R-EXL/-SC

BN

BK (YE)

WH

BU (GN)

CMS-M-EF

7

16

CMS-R-EXN/-SC

BN

WH

3) Old conductor coloring in brackets.

4) There must be no ferromagnetic material in the vicinity of the read head or the actuator. All data refer

to the frontal approach direction and a center offset of m = 0.

5) The LED for the contact status indication has an internal series resistor of 1.5 kΩ.

6) Operating distance for contact status indication and LED.

79,4

25

74

89

A1

A2

13

14

1

2

3

4

5

6

7

8

D1

D2

UB

Figure 1: Dimension drawing Evaluation unit CMS‑E‑AR

Suitable for 35-mm mounting rail