System Manual Safety System CES-A-C5...

6

System Description

The safety switch CES-A-C... meets the following safety requirements:

CES-A-C5E-01: Category 3, PLe according to EN ISO 13849-1
CES-A-C5H-01: Category 4, PLe according to EN ISO 13849-1
Proximity device with self-monitoring type PDF-M according to EN 60947-5-3.
Redundant design of the circuit in the evaluation unit with self-monitoring. As a

result, the safety system is still effective even if a component fails.
The switching state of the semiconductor outputs is checked internally when

the safety guard is opened and closed.

The CES non-contact safety system consists of three components:

Coded actuator
Safety switch with integrated read head
Evaluation unit

On the safety switch CES-A-C... the read head is integrated with the evaluation unit

in a standard housing according to EN 60947-5-.
Each delivered actuator possesses a unique electronic coding and so is a unique

element in the system used. The code in an actuator cannot be reprogrammed.
The evalation unit with integrated read head is fastened to the fixed part of the

safety guard.
The actuator fastened to the movable part of the safety guard is moved towards the

read head by closing the door. When the switch-on distance is reached, power is

supplied to the actuator by the inductive read head and data can be transferred.
The bit pattern read is compared with the code saved in the evaluation unit; if the

data matches, the safety outputs (semiconductor outputs) and the door monitoring

output OUT (semiconductor output) are also set HIGH.
Due to the combination of dynamic polling of the actuator and the redundant,

diverse design of the safety electronics with the two feedback safety outputs, the

evaluation unit will enter the safe state with every detectable fault.
When the safety guard is opened, the safety outputs switch off the safety circuit

and the door monitoring output (OUT) is switched LOW. The state of the safety

outputs is monitored internally by two microprocessors.
On an internal fault in the evaluation unit, the safety circuit is switched off and the

OUT/ERROR LED illuminates red.
The evaluation unit has a redundant switching design with self-monitoring. This

means that the safety system is still effective even if a component fails.