Operating Instructions TZ... Safety Switch

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG

088062-07-12/10 (translation of the original operating instructions)

1

6

5

4

3

2

9

11

10

5

4

6

3

7

2

8

1

7

8

9

10

11

17

16

15

18

1

2

3

4

5

14

13

6

19

12

View on the connection side of the safety switch

TZ..RC18

TZ..SR6

TZ..SR11

Fig. 2b: Connector assignment

(F

Zh

=

F

max

) = 1500 N

1.3

f

Version TZ.. with cable entry

f

TZ..M: Fit cable gland M20 x 1.5 with appropriate
degree of protection.

f

For terminal assignment see Figure 2a.

f

Tighten screws for connections to the switching
element to 0.5 Nm.

f

Tighten the connection terminals with a torque of 0.5 Nm.

f

Check that the cable entry is sealed.

f

Close switch cover and tighten screws to 1.2 Nm.

f

Fit sealing to the mechanical release using the parts
supplied to prevent usage of the mechanical release
during operation.

f

Version TZ..SR, TZ..RC18 and TZ..RC18...C1826
(plug connector)

f

For connector assignments see Figure 2a-2b.

PE

3

1

14

13

21

22

6

2

UK

SK

13

21

22
14

14

22

21
13

4

3

5

6

LED RD

2

1

16

15

41
33

42
34

14

8

7
13

10

22

21
13

14

18

17

9

3

12

11

21

22

6

LED GN

5

4

PE/12

11

1

2

19

UK

SK

34

42

33

41

SK

UK

3

8

6
9

PE

4

2

LED GN

22

21
13

14

11

10

1
7

5

1

2

LED RD

6

5

3

4

4

3

5

6

LED RD

2

1

LED GN

5

4

Illustration: Safety guard closed, actuator locked

TZ..SR6

TZ..SR11

TZ..RC18

4

3

5

6

LED RD

2

1

16

15

41
33

42
34

14

8

7
13

10

22

21
13

14

18

17

9

3

12

11

21

22

4

LED GN

19

6

PE/12

11

1

2
5

UK

SK

34

42

33

41

TZ..RC18...C1826

Fig. 2a: Terminal assignment

f

Electrical function test

1. Switch on operating voltage.
2. Close all safety guards.

Guard locking by solenoid force:

¨

Activate

guard locking.

f

The machine must not start automatically.

f

It must not be possible to open the safety guard.

3. Enable operation in the control system.

f

It must not be possible to deactivate the guard locking
as long as operation is enabled.

4. Disable operation in the control system and

deactivate guard locking.

f

The safety guard must remain locked until there is no
longer any risk of injury.

f

It must not be possible to start the machine as long as
the guard locking is deactivated.

Repeat steps 2 - 4 for each safety guard.

Inspection and service

If damage or wear is found, the complete switch
and actuator assembly must be replaced.
Replacement of individual parts or assemblies is
not permitted!

No servicing is required, but regular inspection of
the following is necessary to ensure trouble-free long-
term operation:

f

correct switching function

f

secure mounting of components

f

dirt and wear

f

sealing of cable entry

f

loose cable connections or plug connectors.

Note:The year of manufacture can be seen in the bottom,
right corner of the rating plate.

Exclusion of liability under the following
circumstances

f

incorrect use

f

non-compliance with safety regulations

f

non-compliance with safety regulations

f

failure to perform functional checks.

EC declaration of conformity

The manufacturer named below herewith declares that
the product fulfills the provisions of the directive(s) listed
below and that the related standards have been applied.
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany
Directives applied:

f

Machinery directive 2006/42/EC

Standards applied:

f

EN 60947-5-1:2004 + Cor.:2005 + A1:2009

f

EN 1088:1995+A2:2008

Leinfelden, July 2010
Dipl.-Ing. Michael Euchner
Director
Duc Binh Nguyen
Authorized representative empowered to draw up
documentation
The signed EC declaration of conformity is included
with the product.

Technical data

Parameters

Value

Housing material

Anodized die-cast alloy

Degree of protection acc. to IEC 60529
Cable entry

IP67

Plug connector

IP65

(SR6/SR11/RC18)

(with tightened mating connector)

Mech. operating cycles

1 x 10

6

Ambient temperature

-25 °C ... +80 °C

Installation position

Any

Approach speed

20 m/min

Actuation frequency

1200/ h

Actuating force at 20 °C

35 N

Extraction force

30 N

Retention force

10 N

Locking force F

max

2000 N

Locking force F

Zh

in acc. with GS-ET-19
Weight

approx. 1.2 kg

Switching principle

Slow-action switching contact

Contact material

Silver alloy, gold flashed

Connection type
TZ..M

Screw terminals M20 x 1.5

TZ..SR6/SR11/RC18

Connector

Connection cross-section (rigid/flexible)
TZ..M

0.34 ... 1.5 mm

2

For mating connector

SR6

(0.5-1.5) mm

2

SR11

0.5 mm

2

RC18

19x(0.75-1.0) mm

2

RC18..C1825

16x(0.38-0.5), 3x(0.75-1.0) mm

2

Rated insulation voltage
TZ..M, TZ..SR6

U

i

= 250 V

TZ..SR11

U

i

= 50 V

TZ..RC18

U

i

= 110 V

Rated impulse withstand voltage
TZ..M, TZ..SR6

U

imp

= 2.5 kV

TZ..SR11, TZ..RC18

U

imp

= 1.5 kV

Rated short-circuit current

100 A

Degree of contamination
(external, acc. ?to EN 60947-1)

3 (industrial)

Switching current, min.,
at 24 V

1 mA

Switching voltage, min.,
at 10 mA

12 V

Utilization category to IEC 60947-5-1
TZ..M, TZ..SR6

AC-15 4A 230V / DC-13 4A 24V

TZ..SR11

AC-15 4A 50V / DC-13 4A 24V

TZ..RC18

AC-15 4A 110V / DC-13 4A 24V

Conventional
thermal current I

th

4 A

Short circuit protection
according to IEC 60269-1

4 A gG

Solenoid operating voltage
TZ..024

AC/DC 24 V (+10%/-15%)

TZ..110

AC

110 V (+10%/-15%)

TZ..220

AC

230 V (+10%/-15%)

Solenoid duty cycle

100 %

Solenoid power consumption

10 W

Limitations at ambient temperature above +70 ... +80 °C
Utilization category
TZ..SR6

AC-15 2A 230V / DC-13 2A 24V

TZ..SR11

AC-15 2A 50V / DC-13 2A 24V

Conventional
thermal current I

th

2 A

Short circuit protection
to IEC 60269-1

2 A gG

Reliability figures according to EN ISO 13849-1

B

10d

3 x 10

6

Functional check

Warning! Danger of fatal injury as a result of faults
in installation and functional check.
Before carrying out the functional check, make sure
that there are no persons in the danger area.
Observe the valid accident prevention regulations.

After installation and any fault, the safety function must
be fully checked. Proceed as follows:

f

Mechanical function test

The actuator must slide easily into the actuating head.
Close the safety guard several times to check the
function.