N o t e – ETC Sensor+ Rack (SR+ HSR+) CEM+ to CEM3 Retrofit User Manual
Page 10
8
CEM3 Sensor+ Rack Retrofit Manual
Step 5:
Make the power and data connections on the backplane.
a: Install the dimmer output ribbon cables. Open the black retaining tabs for each
connector until they are at a 45° angle to the backplane. Press the connectors
into their respective locations until the tabs lock in place at a 90° angle to the
backplane. Make sure the proper side is facing up on each connector and
that each connector is fully seated.
b: Install the power harness (Look at the pin shapes for proper orientation. It will
only fit one way.)
c: Install the DMX connections. (The wires travel out of the top on both styles of
connectors.)
d: Install the 3-pin beacon connector (The wires travel out of the bottom of the
CEM3.)
e: Connect the CAT5 Ethernet cable to the RJ-45 connector on the CEM3
backplane. (Not shown in the drawing below for clarity.).
Step 6:
Push the backplane completely into place in the rack. Be careful not to disrupt
the power and data connections you just made. Make sure none of the wiring
becomes stressed or pinched.
Step 7:
Insert the backplane tabs in the side of the rack.
Step 8:
With the tabs fully inserted in the
sides of the rack, pull the
backplane towards the front of
the rack to line up the screw
holes in the upper side corners
to line up.
Step 9:
Install one screw with a sleeve in
each side upper-corner of the
backplane.
N o t e :
You cannot use the old screws without the additional shoulder-sleeve as they will
block the CEM3 from being fully inserted.
DMX A
DMX B
DMX Thru
Beacon
Power
CEM3 Ribbon Cable Layout
1
2
3
4
(25-48)
(73-96)
(49-72)
(1-24)
Screw with
sleeve