5 external resistor, 6 latch mode (lm), 3 status indications – ElmoMC SimplIQ Analog Servo Amplifiers-Ocarina Installation User Manual
Page 25

Ocarina/Castanet Installation Guide
Servo Control Operation
4-3
MAN-OCSIG (Ver. 1.4)
4.2.5
External Resistor
Connect an external resistor between terminal J1/14 (ECLP) and terminal J1/8 (ECLRET).
The resistor value is given by:
0 < R
ECLP
< 36.4 K (1/8 Watt)
At RECLP greater than 36.4 K, the current limit will be internally clamped to the nominal
value.
IP(nom) is the nominal peak current limit of the amplifier.
(K
R
ECLP
ohm) = 37.4 *
Ip(new)
Ip(nom)
- 1
(K
R
ECLP
(K
R
ECLP
ohm) = 37.4 *
ohm) = 37.4 *
Ip(new)
Ip(nom)
- 1
4.2.6
Latch Mode (LM)
By connecting J1/7 to J1/15, the amplifier is latched to disable mode whenever a Short,
Commutation or Over Temperature failure occurs. Disabling the amplifier temporarily by
removing the power from Enable pin J1/1 resets the latch. Be sure to restore the Enable
connection when the reason for the event no longer exists.
4.3
Status Indications
The following table lists the Ocarina and Castanet amplifier status indications.
Function
Latch
Option
AOK SO1 SO2 SO3
1 Amplifier
OK
(AOK)
N/A Low
Open
collector Open collector Open collector
2
External disable
No
Low
Low
Open collector Low
3 Current
limit
No Low
Open
collector Open collector Low
4 Short
Yes Open
collector Low Open
collector
Low
5
Over temperature Yes
Open collector Open collector Low Low
6 Internal
supplies
protection
No Open
collector Low Low Open
collector
7
Under voltage
No
Open collector Low
Open collector Open collector
8
Over voltage
No
Open collector Open collector Low Open
collector
9 Shunt*
No Low
Open
collector Low Open
collector
10 Power up reset
No
Open collector Open collector Open collector Open collector
11 Commutation
failure
Yes Open
collector Low Low Low
* This indication can be used as a digital input for activating an external shunt regulator.
Table 4-1: Ocarina/Castanet Status Indications