3.

Fire Response.

Expose the sensor under test to

a PSS-ML as described in Step 2. The control
panel should indicate an alarm condition for the
position or zone corresponding to the sensor.

4.

Restore Fire Protection System.

Restore the

system to an operational condition after all tests
have been completed.

MAINTENANCE

The O-ring and the surfaces around the O-ring must
be kept clean to maintain the watertight seal.
Periodically the O-ring should be lubricated to main-
tain the watertight seal and to ensure smooth rotation
of the bezel. Use care when removing the O-ring. Do
not use tools that can damage the O-ring or the seal-
ing surfaces.

When storing the test lamp for long periods of time,
remove the batteries to prevent leakage and possible
damage to the device.

To prolong lamp life after loading fresh batteries, it is
better to turn the light on for several minutes to “age”
the batteries rather than flicking it on and off many
times.

To ensure that active hydrogen removal catalyst is
present in the light, replace the reflector lamp if it gets
wet.

ORDERING INFORMATION

When ordering, please specify:

Part Number

Description

007351-001

PSS-ML Test Lamp

007356-001

Replacement Reflector/Lamp