Appendix c, Pm-5mp+ pm-5mp, Pm-5mp – Det-Tronics PM-5MP & PM-5MP+ Dual Spectrum IR Flame Detector User Manual
Page 12
![background image](/manuals/557712/12/background.png)
10
APPENDIX C
NONINCENDIVE
CLASS B, STYLE B WIRING
Hazardous (Classified) Locations:
Class I, Division 2, Group
A, B, C, D
Class II, Division 2, Group F
, G
Class III, Division 2
Non-hazardous (Non-classified) Locations
Figure C1—Non-Incendive Class B, Style B Wiring (Drawing No. 420033)
PM-5MP
OR
PM-5MP+
PM-5MP
OR
PM-5MP+
PM-5MP
OR
PM-5MP+
V+ (RED)
V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN)
ALARM + (YEL)
ALARM + (GRN)
ALARM – (BLU)
ALARM – (VIO)
TROUBLE + (GRY)
TROUBLE – (WHT)
V+ (RED)
V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN)
ALARM + (YEL)
ALARM + (GRN)
ALARM – (BLU)
ALARM – (VIO)
TROUBLE + (GRY)
TROUBLE – (WHT)
V+ (RED)
V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN)
ALARM + (YEL)
ALARM + (GRN)
ALARM – (BLU)
ALARM – (VIO)
TROUBLE + (GRY)
TROUBLE – (WHT)
END OF LINE
DEVICE
CONTROL ROOM
INSTRUMENTATION
+24 VDC
DC RETURN
ALARM +
ALARM –
HAZARDOUS LOCA
TION:
CLASS I, DIV
. 2, GR
OUPS A, B
, C & D
.
CLASS II, DIV
. 2, GR
OUPS F & G.
CLASS III, DIV
. 1 & 2.
NON-HAZARDOUS LOCA
TION
FIRE SENSOR
ELECTRICAL INTERF
A
C
E
Wire Color
Signal
Red
V+, Input P
o
w
e
r
Or
ange
V+, Input P
o
w
e
r
Blac
k
P
o
w
er Retur
n
Bro
wn
P
o
w
e
r Retur
n
Y
ello
w
A
lar
m +
Green
Alar
m +
Blue
Alar
m –
Violet
Alar
m –
Gr
a
y
T
roub
le +
White
T
roub
le –
NOTES:
1.
FOR INST
ALLA
TION IN NONINCENDIVE,
CLASS I, DIVISION 2, GROUPS
A, B, C &
D; CLASS II, DIVISION 2, GROUPS F & G;
CLASS III, DIVISION 2 HAZARDOUS
(CLASSIFIED) LOCA
TIONS, OR NON-
HAZARDOUS LOCA
TIONS ONL
Y
. WIRING
METHODS SHALL
BE INST
ALLED IN
ACCORDANCE WITH
ANSI/NFP
A
70 (NEC)
AR
TICLE 501-4(b)
AND
ANSI/NFP
A
72.
2.
THIS DRA
WING SHOWS
THREE
SENSORS CONNECTED IN ONE ZONE
IN
A
C
LASS B, STYLE B
CONFIGURA
TION PER NFP
A
7
2.
ADDITIONAL
SENSORS CAN BE
ADDED
BY
REPEA
TING
THE WIRING P
A
TTERN
OF THE
CENTRAL
SENSOR.
3.
PM-5MP
AND PM-5MP+ INTERCONNECT
VIA
FL
YING LEAD.
4.
ELECTRICAL
REQUIREMENT
: 9
T
O
30
VDC
AND 10 MILLIAMPS (MAX) PER
SENSOR.
5.
AN END OF LINE DEVICE,
AS
REQUIRED BY
THE FIRE
ALARM
CONTROL
P
ANEL, IS USED
T
O
MONIT
OR LINE CONTINUITY
.