Calibration

Tools Required: Compressed Calibration Gas Kit

provided by Det-Tronics

Magnet or HART Communicator

Calibration shall be conducted when required as

documented in the Calibration section of the GT3000

instruction manual. It is permissible to conduct

the calibration using either the onboard magnetic

calibration switch or using an approved HART handheld

field communicator. In all cases the GT3000 and

attached transmitter should be allowed to warm up for

one hour minimum before conducting calibration.

Completion of the Response Proof Test must be

recorded and documented in the SIS logbook.

WARNING

Any external alarm equipment, systems or
signaling devices that were disabled must be
re-activated at the conclusion of proof testing
activities.

FAULT/FAILURE ACTIoN PLAN
In the event that a Calibration does not result in an

acceptable Response Proof test, then the standard

Maintenance and Device Repair and Return

procedures as listed in the GT3000 instruction manual

must be followed. Any failure to successfully complete

the Response Proof Test must be recorded and

documented in the SIS logbook.

PRoDUCT REPAIR
Field repair of the GT3000 is limited to replacement of

the filter and/or sensor module. All other device repairs

must be conducted at the factory. No firmware changes

are permitted or authorized. All failures detected

by the device diagnostics or by the Proof Tests that

cannot be resolved through the procedures described

in the FAULT/FAILURE ACTION PLAN section must be

reported to the manufacturer.

oPERATING, ENVIRoNMENTAL, AND
PERFoRMANCE SPECIFICATIoNS
The Safety-Certified GT3000 product versions fully

comply with, and must be operated in accordance

with the functional, environmental, and performance

specifications provided in the GT3000 instruction

manual. A 24 hour mean time to repair should be

assumed for safety availability calculations. All GT3000

diagnostics have a maximum one hour test interval.

SPARE PARTS
Refer to “Ordering Information” in the GT3000

instruction manual. Safety Certification is based on a

sufficient number of spares to achieve a 24 hour mean

time to repair.