15
Operating Modes
The Protocol Plus control has five modes of operation available:
Stopped Mode:
All control and relay outputs are off. Stopped Mode is integrated
into each of the following four modes of operation.
Manual Mode:
Control operates as a single setpoint control until Stopped mode is
accessed
Timer Mode:
Control operates as a single setpoint control until preset time period
has expired.
Profile Mode:
Control operates as a ramp/soak profiling control until the end of
the profile. 8 profiles are available with up to 8 ramp/soak segments
in each profile.
Auto Start Mode (optional):
Control may automatically start Manual, Timer, or
Profile mode based on a preset time and day.
Requires the optional real-time clock feature.
The optional event outputs can be utilized during Manual, Timer, or Profile modes.
Setup Mode
The control has a Setup Mode which provides access to control configuration and
programming of profiles. The Setup Mode contains ten separate electronic Pages where
the configuration and programming parameters (Menu items) are found. The Setup
Mode Pages are described in detail elsewhere in this manual.
Fast Start Mode
The Protocol Plus control has the ability to automatically start an operating mode when
power is applied. This feature may be useful if the same mode of operation is used
everyday. The user can turn on the power and the oven will start the desired process
automatically. The Fast Start Mode is controlled by the Power-Up Start parameters on
the Control page (see Setup Mode).