Table 2 Operating Parameter Outline

Code

Name

Settings

CtL

Control Mode

PID

At

Auto-tuning

OFF

P *

Proportional Band

5 **

I

Integral Time

120

d

Derivative Time

0

Ct

Cycle Time

1

FL

Input Filter

2

bS

PV Bias (Offset)

0

LoC

Key Lock

0

* If P is not displayed the Control Mode (CtL)

must be first set to Pid.

** For F change to value 13.


Definitions for Table 2:

CtL

Control Mode - This parameter determines whether controller functions as a time
proportional or an on/off control.


At

Auto-tuning

– Off for PID tuning, ON for controller to tune process.


P

Proportional Band - Expressed in degrees. This value determines the band width on
both sides of the setpoint within which the control provides proportional control.


I

Integral Time - Expressed in seconds. This parameter corrects for errors in actual
temperature versus the setpoint.


D

Derivative Time - Expressed in seconds. This effect of the derivative time is in direct
proportion to the time setting.


Ct

Cycle Time - Expressed in seconds. This is the total time for one ON/OFF cycle of the
controller output during the proportional action.


FL

Input Filter

– Expressed in seconds. This function should be used when the PV may

fluctuate greatly (i.e. input signal contains noise).


bS

PV Bias - Expressed in percent of span. From

–100 to 100% of span, this parameter

used to set the actual oven temperature to the controller display.


LoC

Key Lock - This provides levels of access to the controller.
0 = No key lock, full access to controller.
1 = Prevents changing of all parameters except setpoint.
2 = Prevents all parameters from being changed including the setpoint.
–1 = Set to enter the Setup parameter setting display.


When LoC = -1, the parameters are displayed in the order shown in the Set-Up
Parameters section, below.