OUT OF RANGE SPAN

Out of Range Span The Out of Range Span was designed to eliminate extrane-
ous signals and noise. This Span or window changes with the distance of the
average distance reading. This window will allow only readings that fall within
its limits. If the target is suddenly changed outside of the window limits, the
sensor will wait until a number or echoes specified in the Out of Range Count
are received within a new window before updating the output reading.

To Read the Out of Range Span in a sensor, use the command structure:

Send

Receive

AAh

Start Byte

66h

Start Byte

01h,

Sensor Number

01h

Sensor Number

11h

Command

11h

Command

00h

Data (not used)

##h

Span (High Byte)

00h

Data (not used)

##h

Span (Low Byte)

55h

End Byte

##h

NA

99h

Stop Byte

To change the Out of Range Span in the sensor to 304 mm, use the command
structure;

Send
AAh

Start Byte

01h,

Sensor Number

12h

Command

01h

Data

304 decimal = 130h

30h

Data

55h

End Byte