34— heat pump heating performance continued – Bryant SPLIT-SYSTEM 697C User Manual

Page 34

background image

—34—

HEAT PUMP HEATING PERFORMANCE Continued

* The Btuh heating capacity values shown are net “integrated’’ values from which the defrost effect has been subtracted. The Btuh heating from supplement

heaters should be added to those values to obtain total system capacity.

† The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to

obtain total system kilowatts.

EDB—Entering Dry Bulb

INDOOR

AIR

OUTDOOR COIL ENTERING AIR TEMPERATURES

°

F

–3

7

17

27

37

47

57

EDB

CFM

Capacity

(MBtuh)

Total

Pwr

Capacity

(MBtuh)

Total

Pwr

Capacity

(MBtuh)

Total

Pwr

Capacity

(MBtuh)

Total

Pwr

Capacity

(MBtuh)

Total

Pwr

Capacity

(MBtuh)

Total

Pwr

Capacity

(MBtuh)

Total

Pwr

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

697C060-A Outdoor Section With FK4CNB006 Indoor Section

65

1575

28.0

25.8

3.81

33.2

30.6

4.02

39.1

35.6

4.24

45.3

40.3

4.4

52.8

48.0

4.81

61.2

61.2

5.20

71.0

71.0

5.73

1750

28.3

26.0

3.82

33.5

30.8

4.01

39.4

35.9

4.22

45.7

40.5

4.4

53.2

48.4

4.76

61.7

61.7

5.14

71.7

71.7

5.65

2012

28.6

26.3

3.84

33.9

31.1

4.02

39.7

36.2

4.21

46.1

40.9

4.4

53.7

48.9

4.72

62.3

62.3

5.09

72.0

72.0

5.52

70

1575

27.7

25.5

3.98

32.9

30.3

4.21

38.7

35.3

4.45

44.9

39.8

4.7

52.1

47.5

5.05

60.5

60.5

5.45

70.2

70.2

5.99

1750

28.0

25.7

3.99

33.2

30.5

4.20

39.0

35.6

4.43

45.2

40.1

4.6

52.6

47.8

4.99

61.0

61.0

5.38

71.6

71.6

5.91

2012

28.3

26.0

4.02

33.5

30.8

4.21

39.4

35.9

4.42

45.6

40.5

4.6

53.1

48.3

4.95

61.6

61.6

5.32

71.5

71.5

5.84

75

1575

27.4

25.2

4.16

32.6

30.0

4.41

38.3

35.0

4.67

44.4

39.4

4.9

51.6

47.0

5.29

59.8

59.8

5.72

69.3

69.3

6.27

1750

27.6

25.4

4.16

32.9

30.2

4.40

38.6

35.2

4.64

44.7

39.7

4.9

52.0

47.3

5.23

60.3

60.3

5.64

70.0

70.0

6.17

2012

28.0

25.7

4.19

33.2

30.5

4.41

39.0

35.6

4.63

45.2

40.1

4.8

52.5

47.8

5.18

60.9

60.9

5.57

70.7

70.7

6.10

Multipliers for Determining the Performance With Other Indoor Sections

Indoor

Section

Size

Heating

Indoor

Section

Size

Heating

Capacity

Power

Capacity

Power

F(A,B)4AN(F,B,C)

060

1.00

1.09

CD3(A,B)A

060

1.00

1.17

FB4ANB

070

1.00

1.03

CE3AA

060

1.00

1.10

FC4BN(F,B)

060

1.00

1.09

CJ5A/CK5A/CK5BA

060

1.00

1.12

FC4BNB

070

1.00

1.03

CK5A/CK5A/CK5BX

060

1.00

1.06

FG3AAA

060

1.00

1.13

CK3BA

060

1.00

1.12

FK4BNB

006

1.00

1.01

COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE

FK4CNB

006

1.00

1.00

CC5A/CD5A/CD5BA

060

1.00

1.19

CC5A/CD5A/CD5BA

060

1.00

1.18

CC5A/CD5A/CD5BW

060

1.00

1.10

CC5A/CD5A/CD5BW

060

1.00

1.11

CD3(A,B)A

060

1.00

1.19

CD3(A,B)A

060

1.00

1.18

CE3AA

060

1.00

1.11

CE3AA

060

1.00

1.11

CJ5A/CK5A/CK5BA

060

1.00

1.11

CJ5A/CK5A/CK5BA

060

1.00

1.12

CK5A/CK5A/CK5BX

060

1.00

1.06

CJ5A/CK5A/CK5BN

060

1.00

1.12

CK3BA

060

1.00

1.11

CJ5A/CK5A/CK5BX

060

1.00

1.07

COILS + 355MAV060100 VARIABLE-SPEED FURNACE

CK3BA

060

1.00

1.12

CC5A/CD5A/CD5BA

060

1.00

1.19

COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE

CC5A/CD5A/CD5BW

060

1.00

1.11

CC5A/CD5A/CD5BA

060

1.00

1.17

CD3(A,B)A

060

1.00

1.19

CC5A/CD5A/CD5BW

060

1.00

1.10