Danger, Electrical hazard – Snorkel TB120 2000 User Manual
Page 2
![background image](/manuals/549934/2/background.png)
P/N 0191482
DANGER
ELECTRICAL HAZARD
The TB 120 is an all metal boom, NOT ELECTRICALLY INSULATED, aerial work platform. Do
not operate it near ELECTRICAL conductors. Regard all conductors as being energized. Use
the table and figure below to determine safe clearance from electrical conductors. Table 1 and
Figure 3 are reprinted courtesy of Scaffold Industry Association, ANSI/SIA A95, page 23.
Figure 3 - Minimum Safe Approach Distance (M.S.A.D.)
Table 1 - Minimum safe approach distance (M.S.A.D.)
to energized (exposed or insulated) power lines
Voltage range
(phase to phase)
Minimum safe approach distance
(Feet) (Meters)
0 to 300V
Avoid contact
Over 300V to 50KV
10
3.05
Over 50KV to 200KV
15
4.60
Over 200KV to 350KV
20
6.10
Over 350KV to 500KV
25
7.62
Over 500KV to 750KV
35
10.67
Over 750KV to 1000KV
45
13.72
Danger: - Do not allow machine personnel or conductive
materials inside prohibited zone.
- Maintain M.S.A.D. from all energized lines and parts
as well as those shown.
- Assume all electrical parts and wires are energized
unless known otherwise.
Caution: - Diagrams shown are only for purposes of illustrating
M.S.A.D. work positions, not all work positions.