– 4 –

Class 1

The auto-fill function will energize the fill output when the tank level is at or below

¾ and de-energize when the Master display reads FULL. Auto-fill will also de-

energize the fill output and turn off the auto-fill status light if there is no data

being received on the data line from the Master display (serial error) or if a

transducer error high or low (range error) is encountered.

4 Outputs for the level lights
Four outputs are available to drive external lights to indicate tank level. These

are positive voltage outputs are capable of 7.5A each (Full light is output 4).

Alarm and alarm silence

The alarm output (pin 3) activates when the tank level falls to below ¼ tank or 10

seconds after a data line problem exists. The alarm output is a positive voltage

output capable of 250mA. The alarm silence input (pin 5) will turn the alarm off

during any alarm circumstance. The alarm silence activated by a momentary

ground input.

1-wire serial interface
The 1-wire serial interface is the link between the master tank level module and

any other remote modules. If the output driver module loses the serial link all

outputs will be deactivated and then the output lights will alternate flashing the

upper two lights and the lower two lights, and the auto-fill function will be

deactivated. After 10 seconds in this serial failure condition the alarm will sound

(it can be turned off with the alarm silence switch).

Dim level light outputs
The output lights are set to the dim condition (50% duty cycle) when a ground is

input on pin 6.

Module LED indicators
There are 3 LEDs on the front of the remote driver module. The RED LED

indicates that the circuit board has power. The YELLOW LED indicates the

power stud has power. The GREEN LED indicates the condition of auto-fill mode

and will react the same as the auto-fill status light output (pin 2).