Follow these start-up instruction steps for initial start-up
before room repopulation when using the standard zone
control panel. For normal star t-up, simply turn the
thermostatic head above room temperature.

1.

Adjust the zone panel’s thermostatic head to its
maximum temperature setting. See Fig. 13. Wait
15 - 30 seconds to allow gas supply pressure to fill
the line and stabilize.

2.

Open all gas supply valves to the heater(s) and check
for gas leaks at all connections using approved leak
detectors.

3.

Allow 10 seconds for gas pressure to stabilize within
the gas hose’excess flow valve before lighting the
heater.Open all gas supply valves to the heater(s) and
check for gas leaks.

FIG. 13

4.

Fully depress the button on the safety control valve
while applying flame to the inner cone point. See
Fig.14. (Remove the cap if stif f. Ensure cap is
replaced af ter lighting). Keep the button fully
depressed for about 30 seconds. Release rhe safety
control button. Allow outer combustion cone to heat
up completely.

FIG. 14

5.

Adjust the temperature by decreasing the setpoint on
the thermostatic head to the desired temperature.
The heater will modulate from low heat to high heat
based upon this setting.

INDICATOR

100ºF

38ºC

THERMOSTATIC
HEAD

12

Lighting Instructions

WARNING

Fire or Explosion Hazard

Do not force the safety gas control valve button.

Use only your hand to depress the gas control button.
Never use any tools.

If the button will not depress by normal hand
pressure, the control should be replaced by a
qualified service person.

Force or attempted repair may result in fire or
explosion, causing property damage, severe injury, or
death.

To reduce temperature, turn down the thermostatic control
on the zone panel, or reduce temperature requirements of
room controller.

To shut down the heaters for maintenance, cleaning or
service:

1.

Shut off all gas supply valves to the heaters.

2.

Allow heaters to burn off fuel gas remaining in the
gas supply line.

3.

Tu r n d ow n t h e t h e r m o s t a t i c h e a d o r ro o m
controller to minimum setting.

Shut-Down Instructions