ELECTRICAL DATA

LEGEND

*Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent voltage
imbalance.
% Voltage Imbalance

EXAMPLE: Supply voltage is 460-3-60.

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.

UNIT
579F

NOMINAL
VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER

SUPPLY

No. 1

No. 2

Min

Max

RLA

LRA

RLA LRA

Qty

Hp

FLA

(ea)

Hp

FLA

FLA

LRA

FLA

MCA

MOCP*

180

(15 Tons)

208/230

187

253

28.8

195

28.8

195

3

0.5

1.7

3.7

10.5/11.0

0.57

81/81

100/100

4.6

18.8

0.57

85/86

110/110

460

414

508

14.7

95

14.7

95

3

0.5

0.8

3.7

4.8

0.30

40

50

2.3

6.0

0.30

43

50

575

518

633

10.8

80

10.8

80

3

0.5

0.8

3.0

3.9

0.57

30

40

2.1

4.8

0.57

32

40

216

(18 Tons)

208/230

187

253

30.1

225

28.8

195

3

0.5

1.7

5.0

15.8/15.8

0.57

87/87

110/110

4.6

18.8

0.57

92/92

110/110

460

414

508

15.5

114

14.7

95

3

0.5

0.8

5.0

7.9

0.30

44

50

2.3

6.0

0.30

47

60

575

518

633

12.1

80

10.8

80

3

0.5

0.8

5.0

6.0

0.57

34

40

2.1

4.8

0.57

36

40

240

(20 Tons)

208/230

187

253

37.8

239

30.1

225

2

1

6.6

7.5

25.0/25.0

0.57

116/116

150/150

4.6

18.8

0.57

120/120

150/150

460

414

508

17.2

125

15.5

114

2

1

3.3

7.5

13.0

0.30

57

70

2.3

6.0

0.30

59

70

575

518

633

12.4

80

12.1

80

2

1

3.4

7.5

10.0

0.57

44

50

2.1

4.8

0.57

46

50

300

(25 Tons)

208/230

187

253

41.0

350

37.8

239

2

1

6.6

10.0

28.0/28.0

0.57

130/130

150/150

4.6

18.8

0.57

135/135

175/175

460

414

508

21.8

158

17.2

125

2

1

3.3

10.0

14.6

0.30

66

80

2.3

6.0

0.30

68

80

575

518

633

17.3

125

12.4

80

2

1

3.4

10.0

13.0

0.57

54

70

2.1

4.8

0.57

56

70

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

AB = 452 v
BC = 464 v
AC = 455 v

Average Voltage = 452 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

= 1.53%