beautypg.com

Bryant 581C User Manual

Page 152

background image

152

PERFORMANCE DATA — 581C

COOLING CAPACITIES — 581C024-060 STANDARD UNITS (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evapo-

rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581C048 (4 Tons)

Temp (F)

Air Entering Evaporator -- CFM/BF

Air Ent

1200/0.05

1600/0.07

2000/0.09

Condenser

Air Entering Evaporator -- Ewb (F)

(Edb)

62

67

72

62

67

72

62

67

72

75

TCG

46.3

51.1

55.7

48.8

53.5

58

50.7

54.9

59.1

SHG

39.9

33.8

27.1

46.3

38.6

29.8

50.6

42.7

32

CMP

2.36

2.37

2.38

2.37

2.38

2.39

2.37

2.38

2.39

85

TCG

42.9

49

54

46.2

51.5

56.4

49.2

52.8

57.4

SHG

38.5

33

26.6

45.2

37.9

29.4

49.1

42.2

31.7

CMP

2.69

2.71

2.72

2.71

2.72

2.74

2.72

2.72

2.74

95

TCG

38.7

45.8

51.9

42.6

48.8

54.2

46.8

50.4

55.5

SHG

36.5

31.8

25.9

42.5

37.1

28.9

46.8

41.6

31.4

CMP

3.05

3.08

3.11

3.07

3.1

3.12

3.1

3.11

3.12

105

TCG

34.4

41.1

49.1

39

43.8

51.5

43.3

46.3

52.8

SHG

34.3

30

24.9

39

35.3

28.2

43.3

40.4

30.9

CMP

3.42

3.48

3.53

3.47

3.5

3.54

3.5

3.52

3.54

115

TCG

31.4

36.3

44.7

35.8

38.4

47.3

39.2

40.6

49.5

SHG

31.4

28.1

23.5

35.8

33.3

26.9

39.2

38.1

30.1

CMP

3.85

3.9

3.96

3.9

3.92

3.98

3.93

3.94

4

125

TCG

28.2

31.1

39.8

31.9

33

41.6

35.3

35.4

43.9

SHG

28.1

26.2

21.8

31.9

31.1

25.1

35.3

35.4

28.4

CMP

4.31

4.35

4.42

4.36

4.37

4.44

4.4

4.4

4.46

581C060 (5 Tons)

Temp (F)

Indoor Entering Air -- CFM/BF

Outdoor

1500/0.26

1750/.31

2000/.35

2500/.45

Air Ent

Indoor Entering Air -- Ewb (F)

(Edb)

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

75

TCG

57

60.2

66.5

72

60.3

62.3

68.5

73.8

63.2

64.1

69.7

75.6

67.4

67.4

71.8

77.6

SHG 55.3

50.5

42.4

33.5

58.6

55.2

45.7

35.4

61.3

59.5

48.6

37.4

65.5

65.5

54.4

40.7

CMP

3.1

3.11

3.12

3.14

3.11

3.12

3.13

3.15

3.11

3.12

3.13

3.16

3.12

3.12

3.14

3.17

85

TCG 54.1

56.9

64

70.2

58.3

59.7

65.9

72

60.9

61.4

67.3

73.4

65.3

65.2

69.6

75.3

SHG 52.6

49.1

41.4

33

56.6

54.1

44.8

35

59.2

58.4

48

36.9

63.4

63.4

54.4

40.4

CMP

3.5

3.52

3.54

3.56

3.52

3.53

3.54

3.57

3.53

3.54

3.54

3.58

3.54

3.54

3.56

3.59

95

TCG 50.2

53

61.1

67.5

55

55.6

62.9

69.3

58.6

58.6

64.3

70.6

62.8

62.8

66.4

72.7

SHG 48.8

47.4

40.3

32.2

53.4

52.3

43.8

34.2

56.9

56.8

47.2

36.1

61

61

53.4

40

CMP 3.94

3.95

3.99

4.02

3.97

3.97

4.01

4.03

3.99

3.99

4.02

4.03

4.01

4.01

4.02

4.05

105

TCG 47.4

47.9

56.5

64.3

50.9

51

59.5

66.1

54.7

54.8

60.9

67.4

59.9

60

62.9

69

SHG

46

45.2

38.7

31.1

49.5

49.5

42.6

33.2

53.1

53.2

45.9

35.2

58.2

58.3

52.4

38.8

CMP 4.42

4.42

4.48

4.51

4.44

4.44

4.5

4.53

4.47

4.47

4.51

4.54

4.5

4.5

4.52

4.54

115

TCG 43.1

43.2

50.3

60.8

47.3

47.3

52.6

62.6

50.1

50.1

55.6

63.9

56

55.9

58.2

65.4

SHG 41.8

42

36.4

30

45.9

45.9

40.2

32.1

48.7

48.7

44.1

34.2

54.4

54.3

50.8

37.9

CMP 4.92

4.92

4.98

5.05

4.96

4.96

5

5.07

4.98

4.98

5.02

5.08

5.03

5.03

5.05

5.08

125

TCG

39

39

43.9

55.7

42.3

42.3

46.9

58.5

46.1

46.1

48.2

59.7

50.9

50.9

51.3

61.4

SHG 37.9

37.9

34.1

28.3

41.1

41

38.2

30.8

44.8

44.8

41.6

32.9

49.4

49.4

48.2

36.9

CMP 5.47

5.46

5.52

5.62

5.51

5.51

5.55

5.64

5.54

5.54

5.56

5.66

5.59

5.59

5.59

5.66

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb

Entering Wet Bulb

COMP — Compressor Power kw
SHG

Gross Sensible Capacity (1000 Btuh)

TCG

Compressor Cooling Capicity (1000 Btuh)

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

58

1C02

4-

060

This manual is related to the following products: