DIMENSIONAL DRAWING — 581A240
UNIT
581A
CORNER WEIGHT*
DIMENSIONS
A
B
C
D
A
B
C
D
E
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Ft-in.
mm
Ft-in.
mm
Ft-in.
mm
Ft-in.
mm
Ft-in.
mm
240 270
523
237
541
245
574
260
596
270
3-4
1016
3-7
1092
0-3
76
6-11
1
⁄
2
2121
1-7
13
⁄
16
504
240 485
465
211
486
220
725
329
737
334
4-2
1270
3-5
1041
0-4
1
⁄
2
114
8- 7
1
⁄
4
2623
3-3
5
⁄
8
1006
*Weights are for unit only and do not include options or crating.
UNIT
581A
MAXIMUM SHIPPING
WEIGHT
Lb
Kg
240 270
2514
1140
240 485
2793
1267
NOTES:
1. Dimensions in (
) are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:
a. Rear: 7
Ј
0
Љ
(2134) for coil removal. This dimension
can be reduced to 4
Ј
0
Љ
(1219) if conditions permit
coil removal from the top.
b. 4
Ј
0
Љ
(1219) to combustible surfaces, all four sides
(includes between units).
c. Left side: 4
Ј
0
Љ
(1219) for proper condenser coil
airflow.
d. Front: 4
Ј
0
Љ
(1219) for control box access.
e. Right side: 4
Ј
0
Љ
(1219) for proper operation of
damper and power exhaust (if so equipped).
f. Top: 6
Ј
0
Љ
(1829) to assure proper condenser fan
operation.
g. Bottom: 14
Љ
(356) to combustible surfaces (when not
using curb).
h. Control box side: 3
Ј
0
Љ
(914) to ungrounded surfaces
(non-combustible).
i. Control box side: 3
Ј
6
Љ
(1067) to block or concrete
walls, or other grounded surfaces.
j. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser coil
and the damper/power exhaust as stated in Note No. 5,
a removable fence or barricade requires no clearance.
7. Dimensions are from outside of corner post. Allow
0
Ј
-
5
⁄
16
Љ
(8) on each side for top cover drip edge.
6