7. MAINTENANCE & TROUBLESHOOTING
7.1 Routine
Maintenance
 
The TCS22 requires minimal maintenance. Once every 4 years replace the battery under the 
controller cover. This battery powers the hardware clock during power outages.
Check sensor calibration once every two years.
 
7.2 Troubleshooting 
7.2.1 TCS22 TROUBLESHOOTING
Problem
Check Out Points
Procedure
TCS22 Fails to operate
Check 240 Volt Power
Check TCS22 Circuit breaker
Check 24 Volt Power
Remove power connector from 
controller and Check for 24 volt Power 
from pin 1 to pin 3 on plug 
Check Internal Fuse
Remove screws from the four corner of 
the front panel of the controller. The 
fuse is located in upper left hand corner 
of the controller. 
Blower #1 light is On but 
Blower fails to operate 
Check A/C unit 24 Volt power 
from C to G 
Check controller switch
Remove junction connector J5. Check 
for continuity from pin #3 to pin #6 on 
controller with the Blower light ON. 
Check wiring and connections
Compressor #1 light is On but 
Compressor fails to operate 
Check A/C unit 24 Volt power 
from C to Y 
Check controller switch
Remove junction connector J5. Check 
for continuity from pin #2 to pin #5 on 
controller with the Compressor light 
ON. 
Check wiring and connections
Heater #1 light is On but 
Heater fails to operate 
Check A/C unit 24 Volt power 
from C to W1 
Check controller switch
Remove junction connector J5. Check 
for continuity from pin #8 to pin #11 on 
controller with the Compressor light 
ON. 
Check wiring and connections
Economizer #1 light is On but 
Economizer fails to operate 
Check controller switch
Disconnect E from the terminal strip on 
the TCS22. Check for continuity from E 