6 model nomenclature, 0 specifications, 1 electrical specifications – Bard TCS22-***-003 User Manual
Page 11: 2 mechanical specifications, 3 environmental specifications, Model nomenclature, Specifications, Electrical specifications, Mechanical specifications, Environmental specifications

2100-444-003A
Page 5
1.6 Model
Nomenclature
TCS2 2 - H D M - 001
BASIC MODEL
SOFTWARE
REVISION NUMBER
---- REMOTE COMMUNICATIONS
SENSORS
DISPLAY M - With
H- Humidity & Temperature
D - With X - Without
T - Temperature Only X – Without
E - Ethernet
2.0 SPECIFICATIONS
2.1 Electrical
Specifications
Supply Voltage
208/240 VAC +/- 10% 50/60 HZ
Minimum Circuit Ampacity 3 Amp
Overcurrent Protection
Internal Circuit Breaker - 3 Amp
Controller Analog Inputs
16
Resolution
8 bits/ 0.4% Full Scale
Voltage Range
0 Vdc to +10 Vdc
Current Rating
5.0 mA at +10 Vdc
Binary Relay Outputs
12
Type
Form "A" Relay SPST N.O.
Contact Rating
24 VAC, 5 A Resistive
24
VAC,
2
A
Inductive
2.2 Mechanical
Specifications
Height
26.25
in.,
(667
mm.)
Width
17.00
in.,
(432
mm.)
Depth
5.50 in., (140 mm.)
Material
18 ga galvanized steel with Beige baked polyester enamel.
Mounting
Vertical
Mounting Area Required
27 in. high by 18 in. wide, (686 mm. high by 457 mm. wide)
Weight
27
lb.,
(12.3
kilograms)
2.3 Environmental
Specifications
Operating Temperature Range
32 to 130 o F (0 to 55
o
C)
Operating Humidity Range
10 to 95%, non condensing
Storage Temperature Range
-35 to 180 o F (-37 to 82
o
C)
Storage Humidity Range
5 to 95%, non condensing