Page 35: Free cooling on / off, Room occupied yes/no, Outdoor enthalpy

2100-444-003A
Page 29
Setpoint will be 70
o
the same as the fixed Dehumidification Heating Setpoint.
5.3.1.7 FREE COOLING
ON / OFF
 
This display item indicates whether outside conditions are suitable to allow the use of outside air 
to provide free cooling inside the structure. The controller calculates the either outside temperature or 
enthalpy from the Outdoor Temperature and Outdoor Humidity and compares this value with the Free 
Cooling Setpoint. The Free cooling setpoint can be either a dry bulb temperature or enthalpy. This is 
user selectable. If outdoor temperature or enthalpy, whichever the user has selected, is less than the Free 
cooling setpoint then Free Cooling is ON. If the temperature or enthalpy of the outside air is more than 
the Free Cooling Setpoint then Free Cooling is Off. 
 
 
5.3.1.8 ROOM OCCUPIED YES/NO
 
This display indicates the status of the After-hours Occupancy Override Button. If the display 
shows "NO", the controller is in the unoccupied mode and the unoccupied setpoints prevail. If the 
display shows "YES", the controller is in the occupied mode and the occupied setpoints prevail. 
Depressing the Occupancy Override Switch on the Zone Temperature Sensor for one second triggers the 
Occupied mode for two (2) hours. 
5.3.1.9 OUTDOOR ENTHALPY
 
 
This outdoor enthalpy displays the calculated outdoor air enthalpy. The outdoor enthalpy is
calculated from the outdoor temperature and outdoor humidity sensors and is used to determine wether 
the air is suitable for free cooling or not. 