4 system startup, 1 wallmount startup checklist, System startup – Bard TCS22-***-003 User Manual
Page 25: Wallmount startup checklist

2100-444-003A
Page 19
3.4
System Startup
3.4.1 WALLMOUNT STARTUP CHECKLIST
Operation Procedure
Bypassing TCS22 
Controller 
Disconnect power to the TCS22. Unplug the plug in connectors J4 and 
J5 from the controller 
Apply power to both 
Wall-mounts 
Follow recommended startup procedure in the WallMount
installation
instructions. Compressor damage could occur if startup procedures are 
not followed. 
Compressor Test
Connect jumper wire on A/C unit low voltage terminals from R to Y 
and observe Compressor operation (There will be a Time delay 
between the installation of the jumper and the starting of the 
Compressor. The Compressor Time Delay relay will determine the 
time delay period.). After the Compressor starts, the jumper wire can 
be removed. 
Blower Test
Connect a jumper wire on A/C unit low voltage terminals R to G and 
observe Blower operation (The Blower will continue to run for One (1) 
minute after the jumper is removed). 
Economizer Test
Connect a jumper wire on A/C unit low voltage terminals R to G and 
observe Blower operation. After Blower operation is confirmed, the 
Economizer can be tested. Leave the jumper in place from the previous 
step. Connect a separate jumper on the A/C unit low voltage terminals 
from E to F and observe the Economizer operation (Never connect 
power to terminals E or F). 
Heater Test
Connect a jumper wire on A/C unit low voltage terminals R to W1. 
The Heating contactor will engage when the jumper is connected. The 
Blower will also operate while this jumper is in place. To check the 
operation of the Heater, you will have to check the Discharge Air 
temperature of the A/C unit. 
Disconnect Power to 
WallMount
Air-
Conditioners
Disconnect power to WallMount
air conditioners. Reconnect plug-in
connectors J4 and J5 to the controller. Go to TCS22 Startup Checklist
