beautypg.com

Bryant Air Cooled Condensing Units 569C User Manual

Page 9

background image

Table 5 — American/European Wire Conversions

AMERICAN

EUROPEAN

Industry

Standard Size

American

Conversion

(mm

2

)

Industry

Standard

Size (mm

2

)

18 AWG

0.82

1.0

16 AWG

1.30

1.5

14 AWG

2.08

2.5

12 AWG

3.30

4.0

10 AWG

5.25

6.0

8 AWG

6.36

10.0

6 AWG

13.29

16.0

4 AWG

21.14

25.0

3 AWG

26.65

2 AWG

33.61

35.0

1 AWG

42.39

50.0

1/0 AWG

53.49

2/0 AWG

67.42

70.0

3/0 AWG

85.00

95.0

4/0 AWG

107.19

120.0

250 kcmil

126.64

150.0

300 kcmil

151.97

350 kcmil

177.90

185.0

400 kcmil

202.63

240.0

500 kcmil

253.29

300.0

600 kcmil

303.95

LEGEND

AWG — American Wire Gage
kcmil — Thousand Circular Mils

VI. ACCESSORY INSTALLATION

At this time any required accessories should be installed on
the unit. Refer to Table 6 for available accessories. Control
wiring information is provided in the unit wiring book.

Table 6 — Accessory List

ACCESSORY

Gage Panel
Winter-Start Relay Package
Weatherprobe™ II Low Ambient Kit
Hail Guard Package (072)
Hail Guard Package (090,102,120)
Thermostats
Subbase

PRE-START-UP

WARNING:

Failure to observe the following warn-

ings could result in serious personal injury:

1. Follow recognized safety practices and wear pro-

tective goggles when checking or servicing refrig-
erant system.

2. Do not operate compressor or provide any electric

power to unit unless compressor terminal cover is
in place and secured.

3. Do not remove compressor terminal cover until all

electrical sources have been disconnected.

4. If refrigerant leak is suspected around compres-

sor terminals, recover refrigerant whenever pos-
sible and relieve all pressure from system before
touching or disturbing anything inside terminal box.

5. Never attempt to repair soldered connection while

refrigerant system is under pressure.

6. Do not use torch to remove any component. Sys-

tem contains oil and refrigerant under pressure.
To remove a component, wear protective goggles
and proceed as follows:

a. Shut off electrical power to unit.

b. Recover refrigerant. Relieve all pressure from

system.

c. Cut component-connecting tubing with tubing

cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to torch
flame.

Proceed as follows to inspect and prepare the unit for initial
start-up:

1. Field electrical power source must agree with unit name-

plate rating.

2. Check voltage imbalance as shown in Table 4, Note 2.

3. Check that all internal wiring connections are tight and

that all barriers, covers, and panels are in place.

4. Ensure all service valves are open. On 576B units, be

sure all compressor service valves are backseated.

5. Verify that compressor holddown bolts have been loos-

ened and that flat/snubber washers can be rotated by
applying finger pressure (snug, but not tight).

6. On 569C and 576B units, verify compressor crankcase

heater is securely in place. Crankcase heater must op-
erate for a least 24 hours before start-up.

7. Note that compressor oil level is visible in the sight

glass (576B units only).

8. Check for leaks in refrigerant system by using soap

bubbles and/or electronic leak detector.

9. Check that liquid line solenoid valve is located at evapo-

rator coil as shown in Filter Drier and Moisture Indi-
cator section, page 6.

10. Check that both outdoor and indoor units are properly

mounted in accordance with installation instructions
and applicable codes.

Fig. 8 — Field Control Wiring Raceway

(576B Unit Shown)

—9—