Bryant Air Cooled Condensing Units 569C User Manual
Page 4
Table 1B — Specifications (SI)
UNIT
569C072
569C090
569C120
576B090
576B102
576B120
NOMINAL CAPACITY (kW)
21
26
35
26
29.9
35
OPERATING WEIGHT (kg)
Aluminum Coils (Standard)
154
168
179
231
256
256
Copper Coils (Optional)
175
199
214
262
287
287
RIGGING WEIGHT (kg)
Aluminum Coils (Standard)
176
191
202
254
279
279
Copper Coils (Optional)
198
221
237
285
309
309
REFRIGERANT*
R-22
COMPRESSOR
Bristol, Reciprocating
Copeland, Scroll
Copeland, Scroll
Reciprocating, Semi-Hermetic
Quantity...Type
1...H26A72Q
1...ZR94KC
1...ZR125KC
1...06DA818
1...06DA824
1...06DH824
(See Note 1)
Quantity Cylinders
2
—
—
4
6
Speed (R/s)
58.4
58.4
58.4
29.2
29.2
Oil Charge (L) (ea)
1.92
2.51
3.25
2.60
3.78
CONDENSER FAN
Propeller; Direct Drive
Quantity...R/s
1...14.2
1...18.3
Diameter (mm)
660
660
Motor Hp (NEMA)
1
⁄
3
3
⁄
4
Nominal Airflow (L/s)
1800
3050
3300
3050
3050
3050
CONDENSER COIL
Enhanced Copper Tubes, Aluminum Lanced Fins
Face Area (sq m)
1.14
1.46
1.90
1.67
1.67
1.67
Storage Capacity (kg)†
5.1
6.75
8.6
7.5
7.5
7.5
CONNECTIONS (sweat)
Suction (in.)
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
Liquid (in.)
1
⁄
2
1
⁄
2
5
⁄
8
1
⁄
2
5
⁄
8
5
⁄
8
CONTROLS
Pressurestat Settings (kPa)
High Cutout
2937
Ϯ
48
Cut-in
2206
Ϯ
138
Low Cutout
48
Ϯ
20
Cut-in
152
Ϯ
34
LEGEND
NEMA — National Electrical Manufacturing Association
*Unit is factory supplied with holding charge only.
†Storage capacity of condenser coil with coil 80% full of liquid R-22 at
51 C.
NOTES:
1. Unit 576B120 has one step of unloading. Full load is 100% capacity,
and one step of unloading is 67% capacity. Unit 576B120 has the
following unloader settings: load is 483
Ϯ
6.9 kPa and unload is
414
Ϯ
13.8 kPa.
2. Equivalent mm values for connectors are as follows:
in.
mm
1
⁄
2
12.7
5
⁄
8
15.9
1
1
⁄
8
28.6
—4—