Bryant Air Cooled Condensing Units 569C User Manual
Page 8
Table 4 — Electrical Data
UNIT
NOMINAL VOLTAGE
(V-Ph-Hz)
VOLTAGE RANGE
COMPRESSOR
OFM
POWER SUPPLY
Min
Max
RLA
LRA
FLA
MCA
MOCP
569C072
208/230-3-60
187
254
21.8
142
1.9
25.6
35
460-3-60
414
508
9.6
72
1.0
12.9
15
575-3-60
518
632
7.6
58
1.9
11.4
15
220-3-50
198
242
19.0
142
1.0
25.6
35
400-3-50
360
440
9.5
72
1.0
12.9
15
569C090
208/230-3-60
187
254
28.8
195
3.8
39.8
45
460-3-60
414
508
14.7
95
1.9
20.3
20
575-3-60
518
632
10.8
80
1.9
15.4
15
220-3-50
198
242
28.8
195
1.5
37.5
45
400-3-50
360
440
14.7
90
1.5
19.9
20
569C120
208/230-3-60
187
254
37.8
239
3.1
46.2
60
460-3-60
414
508
17.2
125
1.4
22.7
30
575-3-60
518
632
12.3
80
1.4
19.3
25
220-3-50
198
242
37.8
239
1.4
46.2
60
400-3-50
360
440
17.2
114
1.4
22.7
30
576B090
208/230-3-60
187
254
31.5
160
3.1
42.5
50
380-3-60
342
418
19.0
75
2.2
26.0
35
460-3-60
414
508
15.7
80
1.4
21.0
25
575-3-60
518
632
12.6
64
1.4
17.2
20
220-3-50
198
253
31.5
160
1.4
42.5
50
400-3-50
342
460
15.7
80
1.4
21.0
25
576B102
208/230-3-60
187
254
39.7
198
3.1
52.7
70
380-3-60
342
418
24.0
93
2.2
32.2
40
460-3-60
414
508
19.9
99
1.4
26.3
35
575-3-60
518
632
15.9
79
1.4
21.3
25
220-3-50
198
253
39.7
198
1.4
52.7
70
400-3-50
342
460
19.9
99
1.4
26.3
35
576B120
208/230-3-60
187
254
39.7
198
3.1
52.7
70
380-3-60
342
418
24.0
93
2.2
32.2
40
460-3-60
414
508
19.9
99
1.4
26.3
35
575-3-60
518
632
15.9
79
1.4
21.3
25
220-3-50
198
253
39.7
198
1.4
52.7
70
400-3-50
342
460
19.9
99
1.4
26.3
35
LEGEND
CSA
— Canadian Standards Association
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code (U.S.A. Standard)
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
UL
— Underwriters’ Laboratories
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. The 575-v units are CSA only.
4. The 380-v units are
not UL or CSA listed.
—8—