Warning, Shock hazard – Bloomfield 9010 User Manual
Page 7

INSTALLATION INSTRUCTIONS (continued)
NOTE: This equipment must be 
installed to comply with 
applicable federal, state and 
local plumbing codes and 
ordinances. 
WARNING:
SHOCK HAZARD
Brewer must be properly 
grounded to prevent possible 
shock hazard. DO NOT 
assume a plumbing line will 
provide such a ground. 
Electrical shock will cause death 
or serious injury. 
 
IMPORTANT: Do not connect 
brewer to electrical power until 
the tank is filled with water. 
Pour water into the pour-over 
opening until water flows from 
the brew head. 
 
IMPORTANT: 
Supply power must match 
nameplate for voltage and 
phase. Connecting to the 
wrong voltage will damage the 
brewer or result in decreased 
performance. Such damage is 
not covered by warranty. 
In some areas, local codes require a backflow preventer (check 
valve) to be installed on the inlet water line. If a backflow 
preventer is used, you must install a water hammer arrester in 
the incoming line, between the backflow preventer and the 
brewer inlet, as far away from the brewer as space will allow. 
This will relieve the excessive back pressures that can cause 
faucet leaks and solenoid malfunctions. 
 
ELECTRICIAN’S INSTALLATION INSTRUCTIONS 
 
REFER TO ELECTRICAL SPECIFICATIONS - Page 1 
Check the nameplate to determine correct electrical service 
required for the brewer to be installed. 
 
IMPORTANT: Before connecting to electricity, make sure 
automatic brewers are connected to the water supply. 
 
Models 9010 & 9012 are equipped with a cord and plug. They 
require a 115 - 125 volt 20 amp circuit (50/60 Hz, 2 wire plus 
ground, with NEMA 5-15R or 5-20R Receptacle). 
 
IMPORTANT: The ground prong of the plug is part of a system 
designed to protect you from electrical shock in the event of 
internal damage. Never cut off the ground prong nor twist a 
blade to fit an existing receptacle. Contact a licensed electrician 
to install the proper circuit and receptacle. 
 
Models 9016 must be wired by an electrician, and require a 
115/230V 20A circuit (50/60 Hz, 2 hot legs / 1 neutral leg, plus 
ground). Remove front panel to gain access to terminal block. 
Green terminal must be connected to a suitable building ground. 
Circuit must be capable of 3800 Watts. See figure 3 at right. 
 
IMPORTANT: Wiring must be installed in approved solid or 
flexible conduit, and must be secured to the brewer with a strain 
relief (to be provided by the installer). 
 
Models 9016EX must be wired by an electrician, and require 
a 220-240V 20A circuit (50/60 Hz, 2 hot legs plus ground). 
Remove front panel to gain access to terminal block. Green 
terminal must be connected to a suitable building ground. 
Circuit must be capable of 3800 Watts. Refer to 9016EX wiring 
diagram on page 23. 
 
IMPORTANT: Wiring must be installed in accordance with local 
codes and ordinances. 
Fig. 3 115/240 Volt Terminal Block
5
601
75815
Owner
s
M
anual In
tegri
ty Decante
r
B
rewers
