Physical data, Vapor line sizing and cooling capacity loss – Bryant AIR CONDITIONER WITH PURONR 113A User Manual
Page 3
3
PHYSICAL DATA
UNIT SIZE SERIES
018---A
024---A
030---A
036---A
042---A
048---A
060---A
Operating Weight (lb)
125
125
134
152
189
210
236
Shipping Weight (lb)
146
146
155
175
218
235
270
Compressor Type
Scroll
REFRIGERANT
Puron® (R---410A)
Control
TXV (Puron® Hard Shutoff)
Charge (lb)
4.25
4.35
4.75
5.25
6.2
8.35
8.75
COND FAN
Propeller Type, Direct Drive
Air Discharge
Vertical
Air Qty (CFM)
1880
2200
2200
2950
3170
3365
4050
Motor HP
1/12
1/10
1/10
1/4
1/5
1/4
1/5
Motor RPM
1100
1100
1100
1100
1100
1100
825
COND COIL
Face Area (Sq ft)
9.85
9.85
11.49
14.77
17.25
21.56
25.15
Fins per In.
20
20
25
25
25
25
25
Rows
1
1
1
1
1
1
1
Circuits
3
3
3
3
4
5
5
VALVE CONNECT. (In. ID)
Vapor
5/8
5/8
3/4
3/4
7/8
7/8
7/8
Liquid
3/8”
3/8”
3/8”
3/8”
3/8”
3/8”
3/8”
REFRIGERANT TUBES* (In. OD)
Vapor (0---80 Ft Tube Length)
5/8
5/8
3/4
3/4
7/8
7/8
1---1/8
Liquid (0---80 Ft Tube Length)
3/8”
* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
PURON 1--STAGE AIR CONDITIONER APPLICATIONS
LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80 ft
or when there is more than 20 Ft vertical separation between
indoor and outdoor units. These applications require additional
accessories and system modifications for reliable system
operation. The maximum allowable total equivalent length is
250Ft. The maximum vertical separation is 200 Ft when outdoor
unit is above indoor unit, and up to 80 Ft when the outdoor unit
is below the indoor unit. Refer to Accessory Usage Guideline
below for required accessories. See Long--Line Application
Guideline for required piping and system modifications. Also,
refer to the table below for the acceptable vapor tube diameters
based on the total length to minimize the cooling capacity loss.
Unit Nominal Size
(Btuh)
Acceptable
Vapor Line
Diameters
(In. OD)
Cooling Capacity Loss (%)
Total Equivalent Line Length (ft)
Standard Application
Long Line Application Requires Accessories
25
50
80
80+
100
125
150
175
200
225
250
18000
1 Stage Puron AC
1/2
1
2
3
3
4
6
7
8
9
10
12
5/8
0
0
1
1
1
1
2
2
3
3
3
24000
1 Stage Puron AC
5/8
0
1
1
1
2
3
3
4
4
5
6
3/4
0
0
0
0
0
1
1
1
1
1
2
7/8
0
0
0
0
0
0
0
0
0
0
1
30000
1 Stage Puron AC
5/8
1
2
3
3
3
4
5
6
7
8
9
3/4
0
0
1
1
1
1
2
2
2
3
3
7/8
0
0
0
0
0
1
1
1
1
1
1
36000
1 Stage Puron AC
5/8
1
2
4
4
5
6
7
9
10
11
13
3/4
0
0
1
1
1
2
2
3
3
4
4
7/8
0
0
0
0
0
1
1
1
1
2
2
42000
1 Stage Puron AC
3/4
0
1
2
2
2
3
4
4
5
6
6
7/8
0
0
1
1
1
1
2
2
2
3
3
1 1/8
0
0
0
0
0
0
0
0
0
0
1
48000
1 Stage Puron AC
3/4
0
1
2
2
3
4
5
5
6
7
8
7/8
0
0
1
1
1
2
2
2
3
3
4
1 1/8
0
0
0
0
0
0
0
0
1
1
1
60000
1 Stage Puron AC
3/4
1
2
4
4
5
6
7
9
10
11
12
7/8
0
1
2
2
2
3
4
4
5
5
6
1 1/8
0
0
0
0
1
1
1
1
1
1
2
Standard Length = 80 Ft or less total equivalvent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See
Long Line Application Guidelines
113A