Physical data, Vapor line sizing and cooling capacity loss – Bryant AIR CONDITIONER WITH PURONR 113A User Manual

Page 3

background image

3

PHYSICAL DATA

UNIT SIZE SERIES

018---A

024---A

030---A

036---A

042---A

048---A

060---A

Operating Weight (lb)

125

125

134

152

189

210

236

Shipping Weight (lb)

146

146

155

175

218

235

270

Compressor Type

Scroll

REFRIGERANT

Puron® (R---410A)

Control

TXV (Puron® Hard Shutoff)

Charge (lb)

4.25

4.35

4.75

5.25

6.2

8.35

8.75

COND FAN

Propeller Type, Direct Drive

Air Discharge

Vertical

Air Qty (CFM)

1880

2200

2200

2950

3170

3365

4050

Motor HP

1/12

1/10

1/10

1/4

1/5

1/4

1/5

Motor RPM

1100

1100

1100

1100

1100

1100

825

COND COIL

Face Area (Sq ft)

9.85

9.85

11.49

14.77

17.25

21.56

25.15

Fins per In.

20

20

25

25

25

25

25

Rows

1

1

1

1

1

1

1

Circuits

3

3

3

3

4

5

5

VALVE CONNECT. (In. ID)

Vapor

5/8

5/8

3/4

3/4

7/8

7/8

7/8

Liquid

3/8”

3/8”

3/8”

3/8”

3/8”

3/8”

3/8”

REFRIGERANT TUBES* (In. OD)

Vapor (0---80 Ft Tube Length)

5/8

5/8

3/4

3/4

7/8

7/8

1---1/8

Liquid (0---80 Ft Tube Length)

3/8”

* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.

Note: See unit Installation Instruction for proper installation.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

PURON 1--STAGE AIR CONDITIONER APPLICATIONS

LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80 ft

or when there is more than 20 Ft vertical separation between
indoor and outdoor units. These applications require additional

accessories and system modifications for reliable system

operation. The maximum allowable total equivalent length is
250Ft. The maximum vertical separation is 200 Ft when outdoor

unit is above indoor unit, and up to 80 Ft when the outdoor unit
is below the indoor unit. Refer to Accessory Usage Guideline

below for required accessories. See Long--Line Application
Guideline for required piping and system modifications. Also,

refer to the table below for the acceptable vapor tube diameters

based on the total length to minimize the cooling capacity loss.

Unit Nominal Size

(Btuh)

Acceptable

Vapor Line

Diameters

(In. OD)

Cooling Capacity Loss (%)

Total Equivalent Line Length (ft)

Standard Application

Long Line Application Requires Accessories

25

50

80

80+

100

125

150

175

200

225

250

18000

1 Stage Puron AC

1/2

1

2

3

3

4

6

7

8

9

10

12

5/8

0

0

1

1

1

1

2

2

3

3

3

24000

1 Stage Puron AC

5/8

0

1

1

1

2

3

3

4

4

5

6

3/4

0

0

0

0

0

1

1

1

1

1

2

7/8

0

0

0

0

0

0

0

0

0

0

1

30000

1 Stage Puron AC

5/8

1

2

3

3

3

4

5

6

7

8

9

3/4

0

0

1

1

1

1

2

2

2

3

3

7/8

0

0

0

0

0

1

1

1

1

1

1

36000

1 Stage Puron AC

5/8

1

2

4

4

5

6

7

9

10

11

13

3/4

0

0

1

1

1

2

2

3

3

4

4

7/8

0

0

0

0

0

1

1

1

1

2

2

42000

1 Stage Puron AC

3/4

0

1

2

2

2

3

4

4

5

6

6

7/8

0

0

1

1

1

1

2

2

2

3

3

1 1/8

0

0

0

0

0

0

0

0

0

0

1

48000

1 Stage Puron AC

3/4

0

1

2

2

3

4

5

5

6

7

8

7/8

0

0

1

1

1

2

2

2

3

3

4

1 1/8

0

0

0

0

0

0

0

0

1

1

1

60000

1 Stage Puron AC

3/4

1

2

4

4

5

6

7

9

10

11

12

7/8

0

1

2

2

2

3

4

4

5

5

6

1 1/8

0

0

0

0

1

1

1

1

1

1

2

Standard Length = 80 Ft or less total equivalvent length

Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines

Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See

Long Line Application Guidelines

113A