DETAILED COOLING CAPACITIES

EVAPORATOR

AIR

CONDENSER ENTERING AIR TEMPERATURES deg F

75

85

95

105

115

125

CFM

EWB

Capacity

MBtuh{

Total

Sys-

tem

KW**

Capacity

MBtuh{

Total

Sys-

tem

KW**

Capacity

MBtuh{

Total

Sys-

tem

KW**

Capacity

MBtuh{

Total

Sys-

tem

KW**

Capacity

MBtuh{

Total

Sys-

tem

KW**

Capacity

MBtuh{

Total

Sys-

tem

KW**

Total

Sens}

Total

Sens}

Total

Sens}

Total

Sens}

Total

Sens}

Total

Sens}

113ANA060---A Outdoor Section With CAP**6024A** Indoor Section

1750

72

67.65

35.66

4.15

64.56

34.48

4.58

61.30

33.25

5.06

57.89

31.98

5.58

54.20

30.63

6.15

50.10

29.15

6.77

67

62.07

43.94

4.10

59.24

42.75

4.53

56.25

41.50

5.01

53.12

40.22

5.54

49.74

38.85

6.11

46.03

37.38

6.74

62

57.01

52.17

4.06

54.45

50.95

4.49

51.79

49.66

4.97

49.04

48.27

5.50

46.34

46.34

6.08

43.50

43.50

6.72

57

55.50

55.50

4.04

53.42

53.42

4.48

51.22

51.22

4.96

48.89

48.89

5.50

46.35

46.35

6.08

43.51

43.51

6.72

2000

72

68.69

37.30

4.26

65.46

36.09

4.69

62.07

34.85

5.16

58.54

33.56

5.69

54.71

32.19

6.26

50.48

30.69

6.87

67

63.07

46.60

4.21

60.11

45.38

4.64

57.00

44.12

5.11

53.75

42.82

5.64

50.27

41.45

6.21

46.44

39.94

6.84

62

58.17

55.80

4.16

55.57

54.47

4.59

52.95

52.95

5.07

50.49

50.49

5.61

47.78

47.78

6.19

44.74

44.74

6.82

57

57.57

57.57

4.16

55.35

55.35

4.59

52.99

52.99

5.07

50.50

50.50

5.61

47.78

47.78

6.19

44.74

44.74

6.82

2250

72

69.44

38.83

4.36

66.10

37.62

4.79

62.61

36.36

5.27

58.97

35.06

5.79

55.04

33.67

6.36

50.70

32.16

6.97

67

63.79

49.12

4.31

60.73

47.89

4.74

57.53

46.62

5.21

54.20

45.31

5.74

50.63

43.90

6.31

46.72

42.34

6.93

62

59.18

59.18

4.27

56.90

56.90

4.70

54.41

54.41

5.18

51.77

51.77

5.72

48.91

48.91

6.30

45.70

45.70

6.93

57

59.25

59.25

4.27

56.90

56.90

4.70

54.42

54.42

5.18

51.78

51.78

5.72

48.91

48.91

6.30

45.70

45.70

6.93

Multipliers for Determining the Performance With Other Indoor Sections

Cooling Indoor Model

Capacity

Power

Furnace Model

*CAP**6024A**

1.00

1.00

CAP**6021A**

0.98

0.98

CNPH*6024A**

0.99

0.99

CNPV*6024A**

0.99

0.99

CSPH*6012A**

1.00

1.00

FV4BNB006

0.99

0.97

FX4CN(B,F)060

1.01

1.01

FY4ANB060

0.98

0.98

CAP**6021A**

0.97

0.97

315(A,J)AV060110

CSPH*6012A**

0.98

0.98

315(A,J)AV060110

CAP**6024A**

0.98

0.98

315(A,J)AV066135

CNPH*6024A**

0.97

0.96

315(A,J)AV066135

CNPV*6024A**

0.97

0.97

315(A,J)AV066135

CSPH*6012A**

0.98

0.97

315(A,J)AV066135

CAP**6024A**

0.98

0.97

315(A,J)AV066155

CNPH*6024A**

0.98

0.97

315(A,J)AV066155

CNPV*6024A**

0.98

0.97

315(A,J)AV066155

CSPH*6012A**

0.98

0.97

315(A,J)AV066155

NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or

indoor unit is located above outdoor unit, a slight variation in capacity may occur.

** Total system kW is total of indoor and outdoor unit kilowatts.
{

Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

}

Sensible capacities shown are based on 80˚F (27˚C) entering air at the indoor coil. For sensible capacities at other than 80˚F (27˚C), deduct 835 Btuh

(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80˚F (27˚C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air

per degree above 80˚F (27˚C).

When the required data fall between the published data, interpolation may be performed.

113A