Table 13 — Accessory/FIOP Static Pressure (in. wg)

LEGEND

NOTES:

1. Heaters are rated at 240 v, and 480 v.
2. The factory assembled horizontal adapter substantially improves

fan performance.

3. The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should then be used in
conjunction with the Fan Performance table to determine blower
rpm, bhp, and watts.

UNIT
551A

HEATER

RATED

VOLTAGE

CFM

ELECTRIC HEATERS

PRESSURE DROP

(kW)

ECONOMI$ER

PRESSURE

DROP

155,180

208/240-3-60

3,750

0.05 (14/19, 26/34)

0.06 (42/56)

0.07 (56/75)

0.03

4,000

0.05 (14/19, 26/34)

0.06 (42/56)

0.07 (56/75)

0.04

5,000

0.07 (14/19, 26/34)

0.08 (42/56)

0.10 (56/75)

0.05

6,000

0.09 (14/19, 26/34)

0.12 (42/56)

0.15 (56/75)

0.07

7,200

0.11 (14/19, 26/34)

0.16 (42/56)

0.20 (56/75)

0.09

7,500

0.12 (14/19, 26/34)

0.17 (42/56)

0.21 (56/75)

0.10

480-3-60

3,750

0.05 (15, 32)

0.06

(55)

0.07 (80)

0.03

4,000

0.05 (15, 32)

0.06

(55)

0.07 (80)

0.04

5,000

0.07 (15, 32)

0.08

(55)

0.10 (80)

0.05

6,000

0.09 (15, 32)

0.12

(55)

0.15 (80)

0.07

7,200

0.11 (15, 32)

0.15

(55)

0.20 (80)

0.09

7,500

0.12 (15, 32)

0.17

(55)

0.21 (80)

0.10

240

208/240-3-60

5,000

0.08 (26/34)

0.11 (42/56)

0.14 (56/75)

0.06

6,000

0.09 (26/34)

0.12 (42/56)

0.15 (56/75)

0.07

7,200

0.11 (26/34)

0.16 (42/56)

0.20 (56/75)

0.09

9,000

0.15 (26/34)

0.19 (42/56)

0.24 (56/75)

0.11

10,000

0.17 (26/34)

0.21 (42/56)

0.26 (56/75)

0.12

11,250

0.20 (26/34)

0.24 (42/56)

0.29 (56/75)

0.14

480-3-60

5,000

0.08 (32)

0.11 (55)

0.14 (80)

0.06

6,000

0.09 (32)

0.12 (55)

0.15 (80)

0.07

7,200

0.11 (32)

0.15 (55)

0.20 (80)

0.09

9,000

0.15 (32)

0.19 (55)

0.24 (80)

0.11

10,000

0.17 (32)

0.21 (55)

0.26 (80)

0.12

11,250

0.20 (32)

0.24 (55)

0.29 (80)

0.14

FIOP — Factory-Installed Option

Fig. 29 — Perfect Humidity™ Operation Diagram