Table 12 —
Fan Perform
ance — 551A240
LEGEND
*Standard low-medium static drive range is 1002 to 1151 rpm. Alternate
high-static drive range is 1193 to 1369. Other rpms require a field-
supplied drive.
NOTES:
1. Maximum continuous bhp for the standard motor is 9.47 (for 208-v
units) and 10.33 (for 230 and 460-v units). The maximum continu-
ous watts is 7915 (for 208-v units) and 8640 (for 230 and 460-v
units). Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
2. Static pressure losses (i.e., EconoMi$er) must be added to exter-
nal static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and casing
losses. See Table 13 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that the
full bhp and watts range of the motor can be utilized with confi-
dence. Using your fan motors up to the watts or bhp rating shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your
Bryant representative for details.
551A240 (20 TONS)*
Cfm
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
6,000
753
2385
2.83
816
2579
3.06
884
2807
3.33
949
3040
3.61
1010
3277
3.89
6,500
793
2738
3.25
861
2959
3.51
925
3186
3.78
987
3418
4.05
1045
3653
4.33
7,000
844
3151
3.74
908
3372
4.00
968
3598
4.27
1026
3828
4.54
1082
4062
4.82
7,500
895
3596
4.27
955
3817
4.53
1013
4042
4.80
1068
4271
5.07
1121
4504
5.34
8,000
947
4073
4.83
1004
4294
5.09
1058
4518
5.36
1111
4747
5.63
1162
4978
5.91
8,500
999
4583
5.44
1053
4803
5.70
1105
5027
5.96
1155
5255
6.23
1204
5485
6.51
9,000
1052
5125
6.08
1103
5345
6.34
1152
5569
6.61
1200
5796
6.88
1247
6025
7.15
9,500
1105
5699
6.76
1153
5919
7.02
1200
6142
7.29
1246
6369
7.56
1291
6598
7.83
10,000
1158
6306
7.48
1204
6526
7.74
1249
6750
8.01
1293
6975
8.27
1336
7203
8.55
551A240 (20 TONS) (cont)*
Cfm
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
6,000
1069
3517
4.17
1125
3761
4.46
1180
4006
4.75
1232
4255
5.05
1283
4506
5.35
6,500
1102
3891
4.62
1156
4132
4.90
1208
4377
5.19
1259
4623
5.48
1308
4871
5.78
7,000
1136
4299
5.10
1188
4538
5.38
1239
4780
5.67
1288
5025
5.96
1335
5271
6.25
7,500
1173
4739
5.62
1223
4977
5.90
1272
5217
6.19
1319
5460
6.48
1365
5705
6.77
8,000
1211
5212
6.18
1259
5449
6.46
1306
5688
6.75
1352
5929
7.03
1396
6172
7.32
8,500
1251
5718
6.78
1297
5954
7.06
1342
6192
7.35
1386
6431
7.63
1429
6673
7.92
9,000
1292
6257
7.42
1337
6492
7.70
1380
6729
7.98
1423
6967
8.27
1464
7207
8.55
9,500
1335
6830
8.10
1377
7063
8.38
1419
7299
8.66
1460
7536
8.94
1501
7776
9.22
10,000
1378
7434
8.82
1419
7667
9.10
1460
7902
9.37
1499
8138
9.65
1538
8377
9.94
551A240 (20 TONS) (cont)*
Cfm
Available External Static Pressure (in. wg)
2.2
2.4
2.6
2.8
3.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
6,000
1332
4750
5.65
1380
5015
5.95
1427
5272
6.25
1472
5531
6.56
1517
5793
6.87
6,500
1356
5122
6.08
1402
5375
6.38
1447
5630
6.68
1492
5886
6.98
1535
6144
7.29
7,000
1381
5519
6.55
1427
5770
6.84
1471
6022
7.14
1514
6276
7.45
—
—
—
7,500
1409
5951
7.06
1453
6199
7.35
1496
6449
7.65
1538
6701
7.95
—
—
—
8,000
1440
6417
7.61
1482
6663
7.90
1523
6911
8.20
—
—
—
—
—
—
8,500
1471
6916
8.20
1513
7161
8.49
—
—
—
—
—
—
—
—
—
9,000
1505
7449
8.84
1545
7693
9.13
—
—
—
—
—
—
—
—
—
9,500
1540
8016
9.51
—
—
—
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
— Brake Horsepower
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor