10

LEGEND

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, and

480 v. Heaters are rated at 240 v, or 480 v. If power distribution volt-
age to unit varies from rated heater voltage, heater kW will vary
accordingly.

†Fuse or HACR circuit breaker.

**Heaters are field installed only.

NOTES:
1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.

3. MCA calculation for units with electric heaters over 50 kW = (1.25 x

IFM amps) + (1.00 x heater FLA).

Table 3 — Electric Resistance Heater Data

*Maximum number of stages using accessory low-ambient kit or head pressure control device and low-ambient kit.

NOTE: Heaters are rated at 240, and 480 v.

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

7
457

UNIT
551A

HEATER kW

HEATER
STAGES

% HEAT

PER

STAGE

MAXIMUM

STAGES*

MINIMUM

HEATER AMPS

Unit Voltages

Heating Cfm

208

230

240

460

480

Cfm

L/s

208

230

240

460

480

155

14

17

19

14

15

1

100

1

3750

1770

39.3

43.4

45.3

17.2

17.9

26

31

34

30

32

2

50/50

2

71.3

78.9

82.3

37.3

39.0

42

52

56

50

55

2

33/67

3

117.0

129.4

135.0

63.3

66.1

180

26

31

34

30

32

2

50/50

2

3750

1770

71.3

78.8

82.3

37.3

39.0

42

52

56

50

55

2

33/67

3

117.0

129.4

135.0

63.3

66.1

56

69

75

73

80

2

50/50

4

155.9

172.4

179.9

92.0

96.0

240

26

31

34

30

32

2

50/50

2

5000

2360

71.3

78.8

82.3

37.3

39.0

42

52

56

50

55

2

33/67

3

117.0

129.4

135.0

63.3

66.1

56

69

75

73

80

2

50/50

4

155.9

172.4

179.9

92.0

96.0