Fault finding logic for 535 se/ld rdb control box – Bosch 25/32kW User Manual

Page 48

background image

Boiler not

operating

with a

heating /

hot water

demand

Burner

motor runs?

L

o

ckout

within 1

second?

Replace

control b

o

x

Replace

motor/pump

Chec

k b

oiler

controls &

supply

Replace

motor

L & N

to

control b

o

x?

Motor or

pump

seized?

Photo cell

functional?

S

olenoid

coil

functional

(100

)?

Replace

photo cell

Motor gives

50 V

olts on

white wire?

L

o

ckout

after 12 sec

purge?

Replace

control b

ox

Replace

solenoid coil

Replace

motor

Ignition

spark

proved?

Oil to pump?

Drive

coupling

broken?

P

urge

pressure

1-2 bar?

P

ump

produces

pressure?

Replace

pump stem

valve,

pressure

OK

?

Replace

solenoid coil

Pipe to

nozzle

holder O

K

?

Replace

nozzle

Replace oil

pump

Replace

control b

o

x

Eectrodes &

leads O

K

?

Yes

No

NO

Yes

No

Yes

No

Yes

Yes

No

No

Yes

Yes

No

No

Yes

Yes

No

Yes

Motor 4

0

between blue &

blac

k wires ?

Replace

control b

o

x

Yes

Yes

No

Yes

No

Yes

No

No

No

Yes

No

Nozzle

atomising

fuel?

Combustion

air setting

correct?

Yes

Yes

Combustion

head set

correctly?

S

olenoid operating?

Increase the pump

pressure, pressure O

K

?

S

olenoid

coil

functional

(100

)?

No

Coil lead

OK

?

Yes

Yes

Replace

control b

o

x

No

Remove

burner

snorkle tube

& retest.

Lights O

K

?

Flame off &

re-lights?

Yes

Photo cell

functional?

No

Yes

Replace

photo cell

No

Boiler or flue

bloc

ked

No

Reseal B

F

Yes

Replace

control b

ox

Yes

Replace

electrodes/

leads

No

Unbloc

k or

replace pipe

No

Reset air

setting

No

Reset

combustion

head

No

FAULT FINDING LOGIC FOR

535 SE/LD RDB CONTROL BOX

All resist

ance measurements are actual measured values and some variation is to be expected

, therefore measured

values should be similar to but not necess

arily identical to the given values

.

T

he operation of the photo cell can be tested by measuring the resist

ance across the photo cell

, it should be a high

resist

ance (

greater than 1

0

M

or open circuit

) in the dark and low resist

ance (3k

or less

) in light

.

Burners on balanced flue systems can recirculate flue products resulting in the burner cycling

, if this happens c

hec

k the

flue system integrity and the terminal position

.

These fault finding charts are provided to assist competent and suitably qualified engineers
to locate and rectify faults. Whilst every effort has been taken to ensure the information
given is correct and complete we cannot guarantee that every eventuality has been
covered.
Worcester, Bosch Group cannot be held responsible for costs incurred by persons not
deemed to be competent.

F

A

UL

T

F

IND

IN

G

& D

IA

G

R

A

M

S

FAULT FINDING

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32

8 716 113 389b (09/07)

47