beautypg.com

Starting the appliance – Bosch 25/32kW User Manual

Page 34

background image

STARTING THE APPLIANCE

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32

8 716 113 389b (09/07)

33

C

O

MMI

S

S

IO

N

IN

G

GREENSTAR HEATSLAVE EXTERNAL

max

flue

reset

boiler

reset

max

lockout

on

service

GREENSTAR HEATSLAVE EXTERNAL

max

flue

reset

boiler

reset

max

lockout

on

service

1

2

3

4

C

GREENSTAR HEATSLAVE EXTERNAL

max

flue

reset

boiler

reset

max

lockout

on

service

STARTING THE APPLIANCE

Domestic hot water:
1

Set the CH/DHW programmer to OFF.

Fully open a hot water tap.

The burner should be OFF and the circulating

pump ON.

2

Close the hot water tap.

Set the DHW thermostat control (C) to

minimum as shown.

Set the programmer to DHW ON.

The burner should be ON with the circulating

pump to heat the water in the Heatslave

external tank.

When minimum set temperature is reached
the burner and circulating pump will switch
off.

3

Fully open a hot water tap.

The burner should be ON with the circulating

pump.
Check the water flow rate using a suitable

measuring container;
12/18KW 15 litres/min
18/25kW 18 litres/min*
25/32kW 22 litres/min*

* Manually regulate using the water main

inlet isolating valve on the boiler.

4

Fully close the hot water tap.

Check the burner and circulating pump**

switch off.

**The high limit thermostat may activate

pump overrun until the correct

temperature is restored.

This manual is related to the following products: