Infiltration rates greater than 0.60 ACH shall not be used. The
minimum required volume of the space varies with the number of

ACH and shall be determined per Table 3 or Equations 1 and 2.
Determine the minimum required volume for each appliance in

the space and add the volumes together to get the total minimum

required volume for the space.
Table 3 -- Minimum Space Volumes were determined by using

the following equations from the National Fuel Gas Code ANSI
Z223.1--2009/NFPA 54--2009, 9.3.2.2:

1. For other than fan--assisted appliances, such as a draft

hood--equipped water heater:

Volume

Other

= 21ft

3

ACH

I

other

1000 Btu/hr

A04002

2. For fan--assisted appliances such as this furnace:

Volume

Fan

= 15ft

3

ACH

I

fan

1000 Btu/hr

A04003

If: Iother = combined input of all other than fan--assisted

appliances in Btuh/hr
Ifan = combined input of all fan--assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and

to the Known Air Infiltration Rate Method.

1. Adjoining rooms can be considered part of a space if:

a. There are no closeable doors between rooms.

b. Combining spaces on same floor level. Each opening

shall have free area of at least 1 in.

2

/1,000 Btuh (2,000

mm

2

/kW) of the total input rating of all gas appliances

in the space, but not less than 100 in.

2

(0.06 m

2

). One

opening shall commence within 12 in. (300 mm) of
the ceiling and the second opening shall commence

within 12 in. (300 mm) of the floor. The minimum
dimension of air openings shall be at least 3 in. (80

mm). (See Fig. 8.)

c. Combining space on different floor levels. The

volumes of spaces on different floor levels shall be
considered as communicating spaces if connected by
one or more permanent openings in doors or floors

having free area of at least 2 in.

2

/1,000 Btuh (4,400

mm

2

/kW) of total input rating of all gas appliances.

2. An attic or crawlspace may be considered a space that

freely communicates with the outdoors provided there are
adequate permanent ventilation openings directly to out-

doors having free area of at least 1--in.

2

/4,000 Btuh of total

input rating for all gas appliances in the space.

3. In spaces that use the Indoor Combustion Air Method,

infiltration should be adequate to provide air for combus-
tion, permanent ventilation and dilution of flue gases.

However, in buildings with unusually tight construction,
additional air MUST be provided using the methods de-

scribed in the Outdoor Combustion Air Method section.

4. Unusually tight construction is defined as Construction

with:

a. Walls and ceilings exposed to the outdoors have a con-

tinuous, sealed vapor barrier. Openings are gasketed or

sealed and

b. Doors and openable windows are weatherstripped and

c. Other openings are caulked or sealed. These include

joints around window and door frames, between sole

plates and floors, between wall--ceiling joints, between
wall panels, at penetrations for plumbing, electrical

and gas lines, etc.

Combination of Indoor and Outdoor Air

1. Indoor openings shall comply with the Indoor Combus-

tion Air Method below and,

2. Outdoor openings shall be located as required in the Out-

door Combustion Air Method mentioned previously and,

3. Outdoor openings shall be sized as follows:

a. Calculate the Ratio of all Indoor Space volume divided

by required volume for Indoor Combustion Air
Method below.

b. Outdoor opening size reduction Factor is 1 minus the

Ratio in a. above.

c. Minimum size of Outdoor openings shall be the size

required in Outdoor Combustion Air Method above
multiplied by reduction Factor in b. above. The min-

imum dimension of air openings shall be not less than
3 in. (80 mm).

INSTALLATION

UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in

bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,

perform the following:

1. Tilt or raise furnace and remove 2 screws holding bottom

filler panel. (See Fig. 9.)

2. Rotate bottom filler panel downward to release holding

tabs.

3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.

Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in

bottom return--air opening. This panel MUST be in place when
only side return air is used.

Bottom
Closure Panel

Bottom Filler Panel

A10273

Fig. 9 -- Removing Bottom Closure Panel

NOTE: Side return--air openings can be used in UPFLOW and
most HORIZONTAL configurations. Do not use side return--air
openings in DOWNFLOW configuration.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 10.) Install field--supplied, 5/16 X 1--1/2 in. (8 X

38 mm) (max) corrosion--resistant machine bolts, washers and
nuts.